Xtreme Power Conversion Corporation
M90S Service Manual
Page 6
Uninterruptible Power Supply
Overload Protection
100%~110%
Alarm and Transfer To Bypass after 30min @ Line mode
Alarm and Cut Off Output after 3min @ Battery mode
110%~130%
Alarm and Transfer To Bypass after 5min @ Line mode
Alarm and Cut Off Output after 30s @ Battery mode
130%~150%
Alarm and Transfer To Bypass after 10s @ Line mode
Alarm and Cut Off Output after 10s @ Battery mode
Over 150%
Alarm and Transfer To Bypass after 200ms @ Line mode
Alarm and Cut Off Output after 200ms @ Battery mode
Auto Retransfer
Yes
Interface
USB 1.1
Yes
Intelligent Slot
SNMP card (Optional)
RS485 card (To be considered)
AS400 card (Optional)
Dry Contact
5 channel Dry Contact Card (Optional)
EPO
Yes
Environment
Operating Temperature
0° to 40°C
Humidity
<95% (No condensing)
Acoustic Noise
≤58dB
Standard
ESD
IEC 61000‐4‐2 Level 4
RS
IEC 61000-4-3 Level 3
EFT
IEC 61000‐4‐4 Level 4
Surge
IEC 61000-4-5 Level 4
Conduction
FCC 47 CFR15, Subpart B
Radiation
Safety
IEC62040‐1‐1
Drop
ASTM D5276-94
Vibration
ASTM D4728-87
Mechanical
Inlet
Terminal Block
Outlet
Terminal Block and Receptacle
Outline Dimension
W x H x D (mm3)
635 *418 *132
- Net Weight (kg)
22
- Packaging Dimension
W x H x D (mm3)
580*250*870
- Gross Weight (kg)
25