background image

Xtreme Power Conversion Corporation

P80 User’s Manual

Page 28

Uninterruptible Power Supply

Battery fault

Sounds every 2 seconds

(At this time, UPS is off to remind users 

that something is wrong with the bat-

tery)

EEPROM error

 

Sounds every 2 seconds

Battery replacement

 

Sounds every 2 seconds

Troubleshooting

If the UPS does not operate correctly, please use the table below to troubleshoot the problems.

Symptom

Possible cause

Remedy

No indication and alarm even 

though the utility is normal.

The AC input power is not con-

nected well.

Check that the input power cord is 

firmly  connected to the utility.

The AC input is connected to the 

UPS output.

Plug the AC input power cord into 

the AC input utility correctly.

The icon 

 

and the warning code 

 are flashing on LCD display and 

alarm is sounding every second.

EPO function is enabled.

Set the circuit to the closed posi-

tion to disable EPO function.

The icon 

 and 

 

are flashing on 

LCD display and alarm is sounding 

every second.

Line and neutral conductors of UPS 

input are reversed.

Have a qualified electrician correct 

the input receptacle wiring.

The icon 

 and 

 are flashing on 

LCD display and alarm is sounding 

every second

The internal battery is incorrectly 

connected.

Check to make sure all batteries are 

properly connected.

Fault code is shown as 27 and the 

icon 

 is showing on LCD display 

and alarm is continuously sound-

ing.

Battery voltage is too high or the 

charger is in fault condition.

Contact your dealer for support.

Fault code is shown as 28 and the 

icon 

 is showing on LCD display 

and alarm is continuously sound-

ing.

Battery voltage is too low or the 

charger is in fault condition.

Contact your dealer for support.

Fault code is shown as 14 and 

alarm is sounding continuously.

The UPS shut down automatically 

because short circuit condition oc-

curred on the UPS output.

Disconnect loads and check output 

wiring or connected devices are in 

short circuit status.

Fault code is shown as 01, 02, 03, 

04, 11, 12, 13 and 41 on LCD dis-

play and alarm is sounding continu-

ously.

A  UPS  internal  fault  has occurred. 

There are two possible results:

1. 

The  load  is  still supplied, but 

directly by AC utility via bypass.

2. 

The load is no longer supplied 

with power.

Contact your dealer for support.

Содержание 800VA P80 Series

Страница 1: ...P80 Pure Sine Wave Line Interactive UPS 800VA 1100VA 1500VA 2200VA 3000VA Models User Installation Manual www xpcc com 2016 Xtreme Power Conversion Corporation All rights reserved Rev 6 29 16...

Страница 2: ...ation and Setup 5 Rear Panel View 6 Operating Principle 6 Install the UPS 7 Setup the UPS 10 Battery Replacement 12 Battery Kit Assembly 15 Operations 19 Button Operation 19 LCDPanel 20 Audible Alarms...

Страница 3: ...Xtreme Power Conversion Limited Warranty 32 Xtreme Power Conversion Load Protection Policy 33 Appendix A P90 BP48 P90 BP72 User Guide 36 Important Safety Instructions 36 Product Overview and Setup 36...

Страница 4: ...ust be easily accessible and close to the UPS system Please use only VDE tested CE marked mains cable e g the mains cable of your computer to connect the UPS system to the building wiring outlet shock...

Страница 5: ...no voltage is present Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified below and any other measures necessary when working wit...

Страница 6: ...Input circuit breaker 5 Network Fax Modem surge protection 6 Emergency power off function connector EPO 7 USB communication port 8 RS 232 communication port 9 SNMP intelligent slot 10 External battery...

Страница 7: ...Supply Install the UPS For safety consideration the UPS is shipped out from factory without connecting battery wires Before install the UPS please follow below steps to re connect battery wires first...

Страница 8: ...Manual Page 8 Uninterruptible Power Supply Step 3 Put the front panel back to the unit Rack mount Installation CAUTION Do NOT use the mounting brackets to lift the unit The mounting brackets are only...

Страница 9: ...Xtreme Power Conversion Corporation P80 User s Manual Page 9 Uninterruptible Power Supply Tower Installation Step 1 Step 2 Step 3...

Страница 10: ...ion connection Communication ports USB port RS 232 port Intelligent slot To allow for unattended UPS shutdown start up and status monitoring connect the communication cable one end to the USB RS 232 p...

Страница 11: ...o External Battery shall be installed by SERVICE PERSONNEL only NOTE It s only allowed to connect external battery boxes up to 1 units Step 7 Turn on the UPS Press the ON Mute button on the front pane...

Страница 12: ...l appear as an orange plug icon located in the system tray near the clock Battery Replacement NOTICE This UPS is equipped with internal batteries and only service person can replace the batteries CAUT...

Страница 13: ...ion Corporation P80 User s Manual Page 13 Uninterruptible Power Supply Step 3 Pull out the battery box by removing two screws on the front panel Step 4 Remove the top cover of battery box and replace...

Страница 14: ...nversion Corporation P80 User s Manual Page 14 Uninterruptible Power Supply Step 5 After replacing the batteries put the battery box back to original location and screw it tightly Step 6 Re connect th...

Страница 15: ...he front panel back to the unit Battery Kit Assembly NOTICE Please assemble battery kit first before installing it inside of UPS Please select correct battery kit proce dure below to assemble it Two B...

Страница 16: ...ible Power Supply Step 3 Put assembled battery packs on one side of plastic shells and insert one more defect battery on the space Step 4 Cover the other side of plastic shell as below chart Then batt...

Страница 17: ...17 Uninterruptible Power Supply Step 2 Connect all battery terminals by following below diagram Step 3 Put assembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic...

Страница 18: ...ion P80 User s Manual Page 18 Uninterruptible Power Supply Six Battery Kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below diagram Step 3 Put assembled battery pac...

Страница 19: ...PS setting mode Switch to UPS self test mode Press and hold ON Mute button for 3 seconds to enter UPS self testing while in AC mode OFF ENTER Button Turn off the UPS Press and hold this button at leas...

Страница 20: ...us Backup time info Input output and Battery info Warning Fault info Setting operation Battery info Display Function Backup Time Information Indicates the backup time in pie chart Indicates the backup...

Страница 21: ...ble management outlets are working Indicates that the UPS alarm is disabled Indicates the UPS powers the output directly from the mains Indicates the battery charger is working Indicates the UPS is wo...

Страница 22: ...Disable ESC Escape ON ON OK OK EP EPO TP Temperature CH Charger RAC Rack display TOE Tower display SF Site Fault EE EEPROM error BR Battery Replacement UPS Setting Parameters 1 Parameters 2 There are...

Страница 23: ...sents output voltage as 115VAC 120 presents output voltage as 120VAC Defualt 127 presents output voltage as 127VAC 02 Programmable Outlets Enable Disable Interface Setting ENA Programmable outlets ena...

Страница 24: ...per charger 05 LCD Display Direction Setting Interface Setting RAC the LCD display is horizontal TOE the LCD display is vertical 06 Autonomy Limitation Setting Interface Setting Parameter 2 Set up bac...

Страница 25: ...on for 3 seconds to enter Setting mode Step 3 Press the Up button ON MUTE to switch to 02 of program list Then press Enter button to enter value setting of parameter 2 Press the Up button to change th...

Страница 26: ...n battery is fully charged the fan will stop working for energy saving Buck mode when AC is normal When the input voltage is higher than the voltage regu lation range but lower than high loss point th...

Страница 27: ...too high 27 X Bus under 03 x Battery voltage too low 28 Inverter soft start fail 11 x Over temperature 41 X Inverter voltage high 12 x Overload 43 Inverter voltage Low 13 x Charger failure 45 X Warni...

Страница 28: ...are reversed Have a qualified electrician correct the input receptacle wiring The icon and are flashing on LCD display and alarm is sounding every second The internal battery is incorrectly connected...

Страница 29: ...ser serviceable parts If the battery service life 3 5 years at 25 C ambient tempera ture has been exceeded the batteries must be replaced In this case please contact your dealer Be sure to deliver the...

Страница 30: ...ICAL Dimensions W x D x H 17 2 x 16 1 x 3 5 in 17 2 x 20 1 x 3 5 in 17 2 x 24 8 x 3 5 in Weight 29 3 lbs 28 7 lbs 44 7 lbs 63 7 lbs 61 9 lbs Line cord 6 ft 5 15P 6 ft 5 15P 6 ft 5 15P 6 ft 5 20P 6 ft...

Страница 31: ...sk you for the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue you a Return Mate rial Authorizati...

Страница 32: ...ipment is repaired or modified by anyone other than XPC Corporation or a XPC Corporation approved third party b the equipment is damaged by the customer is improperly used or stored is subjected to an...

Страница 33: ...otected for the term of the XPC Limited Warranty against certain losses caused by a Power Disturbance for properly connected electronic equipment referred to as the Connected Equipment subject to cert...

Страница 34: ...scretion that the Product has been tampered with or altered in any way What is Not Covered Under the Load Protection Policy The following damage is not covered by this Policy 1 Restoration of lost dat...

Страница 35: ...er Disturbance XPC will in its sole discretion issue payment to the Purchaser for either the cost of repair of the Connected Equipment or the Fair Market Value of the damaged Connected Equipment up to...

Страница 36: ...ox enclosure The battery will discharge naturally if the system is unused for a period of time It should be recharged every 2 3 months if unused If this is not done then the warranty will be null and...

Страница 37: ...necessary to select a proper environment to install the unit in order to minimize the possibility of damage to the battery box and extend the life of the batteries Please follow the instructions belo...

Страница 38: ...ed to operate with the following types of batteries 48V 9Ah Version 4 pieces of 12V 9Ah batteries per string 72V 9Ah Version 6 pieces of 12V 9Ah batteries per string Battery Replacement If your batter...

Страница 39: ...panel part by pulling it from the lower extremity Step 3 Remove the fixed part of the front panel by removing the 2 screw present Step 4 Remove the metal top cover of the battery box by unscrewing 8...

Страница 40: ...e on the battery hold down brackets on the right side of the battery box Step 6 Now it is possible to put all batteries inside the unit by following the below picture the following drawing are indicat...

Страница 41: ...nel and secure it with screws Step 10 Connect the battery box to the UPS P90 BP72 Step 1 Open the package and place the battery box on a horizontal plane Step 2 Remove the removable front panel part b...

Страница 42: ...side of battery box Step 6 Now it is possible to put the batteries inside following below picture in the following drawing are indicated the fasten positions for the correct batteries placing Note To...

Страница 43: ...tep 9 Put the metal top cover back on the unit Close the front fixing plate and the two parts of the front panel and secure it with screws Step 10 Connect the battery box to the UPS Wiring Diagram P90...

Страница 44: ...80M M 220MM 4 260MM 300MM Note The cable connection from the external battery connector to PCB is already present inside the battery box All the other cable connections should be made in accordance wi...

Страница 45: ...le parts If the battery service life 3 5 years at 25 C ambient temperature has been exceeded the batteries must be replaced In this case please contact your dealer Be sure to deliver the spent battery...

Отзывы: