VESDA by Xtralis
VESDA VLI Product Guide
www.xtralis.com
39
Command
Description
Execute From
Detector
VSC
Start Fault Test
Generate a fault on the detector and de-energizes
the fault relay (Relay 2).
Start Alarm Test
Simulate full scale smoke level and initiates all
alarm activity.
Alarm relays will energize unless isolated.
Start Air Flow Fault Test
Test the air flow sensing system by shutting down
the aspirator for 30 seconds.
Relay Test
Test the available relays.
View Current Air Flow
View the current airflow.
Monitor Filter
Display filter status.
Clean Air Zero
Measure chamber background.
Note:
This command will shut down the
aspirator for up to a minute.
Содержание VESDA VLI