Fault No.
Description
Cause
Action
Fault Classification
4
Filter removed
The air filter has been
removed from the
detector
Replace the filter. If
problem persists check
filter switch.
Urgent
8
Aspirator speed control
failure
Aspirator cannot run at
the required speed
possibly due to an
aspirator or speed
sensor failure.
If fault persists contact
your authorized Xtralis
representative.
Minor
11
Filter approaching
capacity
The air filter is possibly
clogged or the dust
count for the filter is
approaching the
maximum threshold.
The filter should be
replaced and the filter
counter reset.
Minor
12
Zone setup = factory
defaults
The detector
configuration has
reverted to the factory
defaults.
Run the ‘Accept Factory
Defaults’ command from
the Device Menu.
If this fault continues
contact your authorized
Xtralis representative.
Urgent
14
Flow sensors = factory
defaults
The flow sensor
calibration is corrupt
Contact your authorized
Xtralis representative for
a replacement detector.
Minor
15
Power supply failure
The source supplying
AC power has failed.
Check the power supply
and restore. If it is not
indicating a fault check
the wiring. If the fault
persists, contact your
authorized Xtralis
representative.
Minor
22
Flow sensor failure
The flow sensor has
failed
Contact your authorized
Xtralis representative for
a replacement detector.
Minor
23
Laser signal too low
The detector has
detected smoke levels
cleaner than is
possible/allowed.
Contact your authorized
Xtralis representative for
a replacement detector.
Urgent
27
AutoLearn aborted
AutoLearn has been
cancelled before the
end of the set period.
This may be due to a
Fire condition being
detected during the
learning period.
Inspect the Smoke
trends using Xtralis
VSC.
Investigate and
eliminate the causes
and re-run AutoLearn,
or set the alarm
thresholds manually.
Urgent
29
Manufacturer setup
corrupted
The manufacturer setup
on the reporting device
has not been altered
from the factory defaults
or has reverted to the
factory defaults.
Contact your authorized
Xtralis representative for
a replacement detector.
Urgent
Table 10-2: VLC-400 Applicable Faults and Classification List (continued...)
Содержание VESDA VLC-400
Страница 1: ...VESDA VLC 400 Product Guide June 2014 Document 03494_11 Part Number 18938...
Страница 2: ......
Страница 8: ...VESDA VLC 400 Product Guide VESDA by Xtralis 2 www xtralis com This page is intentionally left blank...
Страница 10: ...VESDA VLC 400 Product Guide VESDA by Xtralis 4 www xtralis com This page is intentionally left blank...
Страница 24: ...VESDA VLC 400 Product Guide VESDA by Xtralis 18 www xtralis com This page is intentionally left blank...
Страница 28: ...VESDA VLC 400 Product Guide VESDA by Xtralis 22 www xtralis com This page is intentionally left blank...
Страница 30: ...VESDA VLC 400 Product Guide VESDA by Xtralis 24 www xtralis com This page is intentionally left blank...
Страница 38: ...VESDA VLC 400 Product Guide VESDA by Xtralis 32 www xtralis com This page is intentionally left blank...
Страница 42: ...VESDA VLC 400 Product Guide VESDA by Xtralis 36 www xtralis com This page is intentionally left blank...