Maintenance
The VESDA VLC-400 detector requires little regular maintenance as the majority of potential failures are
monitored.
There are only two serviceable items, the filter cartridge and the aspirator.
Note:
The rear cover of the detector MUST NOT be removed, as this will void the warranty.
9.1
Schedule
Table 9-1 lists the maintenance schedule necessary to maintain the VESDA VLC-400 in peak working order.
Action
Frequency
Details
Check power supplies
Every month
Test in accordance with suppliers
instructions.
Note:
Where the condition of the battery
is regularly checked automatically,
less frequent manual checks may
be applicable.
Check pipe work
Every 6 months
Check that all pipe runs are intact, that pipe
supports and joints are firm and that the
sampling holes are free of dirt.
Check air flows
Every year
Check logs to verify that no airflow faults
have occurred.
Where possible use Xtralis VSC to read the
airflow readings (including the raw airflow
readings).
Any sign of drift should be investigated.
Check filter
Every year
Check that there are no filter faults (where
possible use Xtralis VSC to read the current
filter counts).
Change Filter
Every 2 years
Fit a new filter cartridge regularly depending
on the relative cleanliness of the protected
environment. For example, every 2 years in a
normal environment, up to 5 years in a clean,
air conditioned computer room or every year
or less in an area exposed to a dusty or
smoky atmosphere
Smoke test
Every year
Isolate the detector from the FACP. Set the
detector in Test mode and introduce smoke
into the end cap. Refer to Chapter 8 for further
information.
Compare response times with those
previously recorded and investigate any
discrepancies.
Flush sampling points
Every 2 years
Isolate the detector from the FACP, remove
pipe from the inlet port and connect a vacuum
cleaner. Run the cleaner for several minutes.
Clean sampling points
As necessary
If flushing does not clear the sampling points
then they must be physically cleared.
Table 9-1: Maintenance Schedule
Содержание VESDA VLC-400
Страница 1: ...VESDA VLC 400 Product Guide June 2014 Document 03494_11 Part Number 18938...
Страница 2: ......
Страница 8: ...VESDA VLC 400 Product Guide VESDA by Xtralis 2 www xtralis com This page is intentionally left blank...
Страница 10: ...VESDA VLC 400 Product Guide VESDA by Xtralis 4 www xtralis com This page is intentionally left blank...
Страница 24: ...VESDA VLC 400 Product Guide VESDA by Xtralis 18 www xtralis com This page is intentionally left blank...
Страница 28: ...VESDA VLC 400 Product Guide VESDA by Xtralis 22 www xtralis com This page is intentionally left blank...
Страница 30: ...VESDA VLC 400 Product Guide VESDA by Xtralis 24 www xtralis com This page is intentionally left blank...
Страница 38: ...VESDA VLC 400 Product Guide VESDA by Xtralis 32 www xtralis com This page is intentionally left blank...
Страница 42: ...VESDA VLC 400 Product Guide VESDA by Xtralis 36 www xtralis com This page is intentionally left blank...