Factory Default Settings
The VESDA VLC-400 is shipped from the factory with the default settings as shown in Table 6-1.
Only authorized personnel at the Administrative (ADM) or Distributor (DST) level may alter these values (refer
to Section 8.2 on page 29)
These settings can be accessed via the Xtralis VSC menu settings using the minimum access level as
shown in the table.
Parameter
Default Value
Minimum
Access Level
Units
Metric
Adm
Airflow…High Urgent
130%
Adm
Airflow…High Minor
120%
Adm
Airflow…Low Minor
80%
Adm
Airflow…Low Urgent
70%
Adm
AutoLearn
14 days
0 hours
0 minutes
Adm
Smoke Threshold
Mode 3: 0.2%
Delay: 10 secs
Adm
Relay
Fire Command from the Fire Panel
Adm
Ext LED
Fire Command from the Fire Panel
Adm
Device Type
Aspirating Smoke Detector – type
152
Adm
Filter Service Interval
1825 days (5 years)
Adm
Device ID
Name/Location
Adm
Event Log to View
Smoke Level
Alarms
Faults
User Action
Adm
Device Loop Address
0
Adm
Table 6-1: Factory Default Settings
Содержание VESDA VLC-400
Страница 1: ...VESDA VLC 400 Product Guide June 2014 Document 03494_11 Part Number 18938...
Страница 2: ......
Страница 8: ...VESDA VLC 400 Product Guide VESDA by Xtralis 2 www xtralis com This page is intentionally left blank...
Страница 10: ...VESDA VLC 400 Product Guide VESDA by Xtralis 4 www xtralis com This page is intentionally left blank...
Страница 24: ...VESDA VLC 400 Product Guide VESDA by Xtralis 18 www xtralis com This page is intentionally left blank...
Страница 28: ...VESDA VLC 400 Product Guide VESDA by Xtralis 22 www xtralis com This page is intentionally left blank...
Страница 30: ...VESDA VLC 400 Product Guide VESDA by Xtralis 24 www xtralis com This page is intentionally left blank...
Страница 38: ...VESDA VLC 400 Product Guide VESDA by Xtralis 32 www xtralis com This page is intentionally left blank...
Страница 42: ...VESDA VLC 400 Product Guide VESDA by Xtralis 36 www xtralis com This page is intentionally left blank...