VESDA-E VEP-A10-P Product Guide
8
www.xtralis.com
1
25%
2
78%
3
80%
4
60%
Figure 2-5: Airflow Screen
1
25%
2
78%
3
80%
X
0%
Figure 2-6: Airflow Screen with a disabled
Sampling Pipe
Status Screen
The Status screen displays a usage indicator for the filter and status information for the Normalization,
AutoLearn Smoke and AutoLearn Flow functions.
Note:
Refer to Chapter 6 for further information on the Normalization, AutoLearn Smoke and AutoLearn
Flow functions.
0%
%
Figure 2-7: Status Screen
Navigation
Press Left or Right arrows at the bottom of the screen to cycle through the available screens.
2.4
Internal Buttons
AutoConfig
l
To normalize the detector, press and hold the button until the AutoConfig LED illuminates continuously
(approximately 2 seconds), then release the button.
l
To initiate AutoLearn Smoke and Flow, press and hold the AutoConfig button until the AutoConfig
LED starts flashing (approximately 15 seconds), then release the button.
l
Cancel the AutoLearn or Normalization functions by pressing and holding the AutoConfig button for 5
seconds. The LED will turn off. If AutoLearn is halted, the flow and smoke thresholds will be left at the
previous settings.
2.5
Communication Ports
The majority of user operations are performed using software installed on a computer connected to the
detector via one of the physical communication ports. The correct connection method to use depends on the
purpose for connecting to the detector (Figure 2-8).
Содержание VESDA-E VEP-A10-P
Страница 1: ...VEP A10 P 4 Pipes VESDA E VEP A10 P Product Guide September 2020 Doc No 22071_15 Part No AD30311 000 ...
Страница 2: ......
Страница 8: ...VESDA E VEP A10 P Product Guide vi www xtralis com This page is intentionally left blank ...
Страница 12: ...VESDA E VEP A10 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Страница 54: ...VESDA E VEP A10 P Product Guide 46 www xtralis com This page is intentionally left blank ...
Страница 78: ...VESDA E VEP A10 P Product Guide 70 www xtralis com This page is intentionally left blank ...
Страница 96: ...VESDA E VEP A10 P Product Guide 88 www xtralis com 1 2 3 Figure 7 21 Undo Sampling Module screws ...
Страница 102: ...VESDA E VEP A10 P Product Guide 94 www xtralis com This page is intentionally left blank ...
Страница 106: ...VESDA E VEP A10 P Product Guide 98 www xtralis com This page is intentionally left blank ...
Страница 112: ...VESDA E VEP A10 P Product Guide 104 www xtralis com Z zone 55 57 73 99 ...