Regional Regulatory Requirements and Notices
European Installations
EN 54-20
The product must use a power source conforming to EN 54-4 and EN60950-1 Section 2.5.
The product is compliant with EN 54-20 sensitivity requirements provided the following conditions are met:
l
For a Class A detector, hole sensitivity must be better than 1.5% obscuration/m and transport time less
than 60 seconds
l
For a Class B detector, hole sensitivity must be better than 3% obscuration/m and transport time less
than 90 seconds
l
For a Class C detector, hole sensitivity must be better than 8% obscuration/m and transport time less
than 110 seconds
These limits should be verified using ASPIRE during the design of the sampling pipe network.
The product is compliant with EN 54-20 flow monitoring requirements provided the following conditions are
met:
l
The minor low and minor high flow thresholds should be set at 85% and 115% respectively
l
The flow through the detector predicted by ASPIRE must be greater than 20 L/m.
Additional information:
The VESDA-E VEP-A00 passed the EN 54-20 fire tests with the following configurations:
l
Class A with 40 holes and a Fire-1 setting of 0.028% obs/m
l
Class B with 80 holes and a Fire-1 setting of 0.027% obs/m
l
Class C with 100 holes and a Fire-1 setting of 0.072% obs/m
Only applies to VEP-A00-P.
Japanese Installations
To comply with Japanese local code requirements the WiFi capability shall be disabled.
Product Listings
l
UL
l
ULC
l
FM
l
ActivFire
l
CE
l
VdS
l
EN 54-20
l
ISO 7240-20
l
NF
Regional approvals listings and regulatory compliance vary between product models. Refer to www.xtralis.com for
the latest product approvals matrix.
Document:
22060_1
5
Part Number: AD30274-000
Содержание VESDA-E VEP-A00
Страница 2: ......
Страница 8: ...VESDA E VEP A00 P Product Guide vi www xtralis com This page is intentionally left blank ...
Страница 10: ...VESDA E VEP A00 P Product Guide 2 www xtralis com A 4 Air Sampling Test Results 93 B Glossary 95 Index 97 ...
Страница 12: ...VESDA E VEP A00 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Страница 22: ...VESDA E VEP A00 P Product Guide 14 www xtralis com This page is intentionally left blank ...
Страница 94: ...VESDA E VEP A00 P Product Guide 86 www xtralis com 1 2 3 Figure 7 21 Undo Sampling Module screws ...
Страница 102: ...VESDA E VEP A00 P Product Guide 94 www xtralis com This page is intentionally left blank ...
Страница 108: ...VESDA E VEP A00 P Product Guide 100 www xtralis com This page is intentionally left blank ...