- 68 -
System return
:
CGI Command : Data follows
c61=0.000000, c62=0.000000, c63=0.000000, c64=0.000000, temp=22.700001
C61 to C64 means 4 currents
,
temp is temperature
(
as Celsius
)
2.5
To get temperature
(
Celsius
)
: gettemp
http://192.168.1.150/set.cmd?cmd=gettemp
System return
:
CGI Command : Data follows
temperature=22.700001
2.6
To set the power on / off
:
setpower&p6x=0 or 1
p6x=0 means off
,
p6x=1means ON
,
x can be 1 to 4 ( power1 to power 4)
Example : Turn on POWER1 and POWER2 and turn off POWER3
:
http://192.168.1.18/set.cmd?cmd=setpower&p61=1&p62=1&p63=0
System return
:
CGI Command : Data follows
p61=1,p62=1,p63=0
2.7
Setup power to reboot as RESET
:
setpowercycle& p6x=delayTime
X can be 1to 4 ( power 1 to power 4 )
,;
dealyTime mean the time ( second) waiting
for reset
For example :
http://192.168.1.18/set.cmd?cmd=setpowercycle
&p61=5&p62=2&p63=4
System return
:
CGI Command : Data follows
p61 cycle ok,p62 cycle ok,p63 cycle ok