DUCT FITTINGS:

This Hood Must Use an

6" Round Duct. It Can

Transition to 3-1/4" x

10" or 3-1/4" x 12" Duct.

Use  this  chart  to  compu-

te  maximum  permissible 

lengths  for  duct  runs  to 

outdoors.
NOTE: 

Do not exceed maxi-

mum permissible equivalent 

lengths!

Maximum  duct  length: 

100  feet  for  range  ho-

ods.
Flexible ducting:

If  flexible  metal  ducting 

is used, all the equivalent 

feet  values  in  the  table 

should  be  doubled. The 

flexible metal duct should 

be  straight  and  smooth 

and extended as much as 

possible.
DO NOT use flexible plastic 

ducting.
NOTE: 

Any home ventilation 

system, such as a ventilation 

hood,  may  interrupt  the 

proper flow of combustion 

air  and  exhaust  required 

by fireplaces, gas furnaces, 

gas water heaters and other 

naturally vented systems. To 

minimize the chance of in-

terruption of such naturally 

vented systems, follow the 

heating equipment manu-

facturer’s  guidelines  and 

safety  standards  such  as 

those published by NFPA.

Duct 

Piece:

Dimensions:

Equivalent 

Number 

Length*:

Quantity

Used:

Total

Equivalent

Length:

Round, straight 1 ft. (per foot 

lenhgth)

3-1/4" x 10" 

straight

1 ft. (per foot 

lenhgth)

90° elbow

12 ft.

45° elbow

7 ft.

3-1/4" x 10"

3-1/4" x 12"

90° elbow

14 ft.

10 ft.

3-1/4" x 10"

3-1/4" x 12"

45° elbow

8 ft.

6 ft.

3-1/4" x 10"

3-1/4" x 12"

90° elbow

33 ft.

24 ft.

6" round to 

rectangular

2 ft.

Rectangular to 

8" round

2 ft.

3-1/4" x 10"

3-1/4" x 12"

6" round to 

rectangular 

transition 90° 

elbow

4 ft.

4 ft.

3-1/4" x 10"

3-1/4" x 12"

Rectangular to 

6" transition 

90° elbow

4 ft.

4 ft.

Round wall 

cap with 

dramper

24 ft.

3-1/4" x 10"

3-1/4" x 12"

Rectangular 

wall cap with 

dramper

24 ft.

18 ft.

Round roof 

cap

33 ft.

*Actual  length  of  straight  duct  plus  duct 

fitting  equivalent.  Equivalent  length  of  duct 

pieces  reflect  requirements  for  good  venting 

performance with any ventilation hood.

Total Duct Run =

Содержание XOI27S

Страница 1: ...CTORA Manual de utilización USA F E XOI27S NEED HELP Call our ventilation experts toll free al 800 966 8300 AVEZ VOUS BESOIN D AIDE Contactez nos experts au numéro gratuit 800 966 8300 NECESITA AYUDA Póngase en contacto con nuestros expertos a través del número gratis 800 966 8300 ...

Страница 2: ...the original purchaser for products purchased for ordinary home use in North America Should you require service for your XO product call a product service specialist at 800 966 8300 Improper Installation Service trips to the home to teach you how to use the product Resetting circuit breakers Damage caused after delivery EXPECT MORE FROM XO When buying any XO appliance you can be confident you have...

Страница 3: ...erials and vapors CAUTION To avoid motor bearing damage and noisy and or unbalanced impellers keep drywall spray construction dust etc off power unit CAUTION Please read specification label on product for further information and requirements WARNING TO REDUCETHE RISK OF FIRE ELECTRIC SHOCK OR INJURYTO PERSONS OBSERVE THE FOLLOWING A Use this unit only in the manner intended by the manufacturer If ...

Страница 4: ... you have a Class ABC extinguisher and you already know how to operate it 2 The fire is small and contained in the area where it started 3 The fire department is being called 4 You can fight the fire with your back to an exit aBased on kitchen firesafety tips published by NFPA Proper maintenance of the Range Hood will assure proper performance of the unit INSTALLATION INSTRUCTIONS WARNING TO REDUC...

Страница 5: ...f the appliance C No food must be cooked flambè underneath the hood D The use of an unprotected flame is dangerous for the filters and could cause fires E Watch constantly the fried food in order to avoid the cooking oil flares up F Before performing any mainteinance operation disconnect the hood from the electrical service The manufacturers will not to accept any responsability for eventual damag...

Страница 6: ...terruption of such naturally vented systems follow the heating equipment manu facturer s guidelines and safety standards such as those published by NFPA Duct Piece Dimensions Equivalent Number Length Quantity Used Total Equivalent Length Round straight 1 ft per foot lenhgth 3 1 4 x 10 straight 1 ft per foot lenhgth 90 elbow 12 ft 45 elbow 7 ft 3 1 4 x 10 3 1 4 x 12 90 elbow 14 ft 10 ft 3 1 4 x 10 ...

Страница 7: ...pe or Duct Tape INSTALL THE DUCTWORK NOTE To reduce the risk of fire use only metal ductwork 1 Decide where the ductwork will run between the hood and the outside 2 A straight short duct run will allow the hood to perform most efficiently 3 Long duct runs elbows and transitions will reduce the performance of the hood Use as few of them as possible 4 Install a roof or wall cap Connect 6 round metal...

Страница 8: ... 8 Hood Specifications Front of hood Side of hood Top of hood Mounting height and clearance Product dimensions and clearance XOI27S ...

Страница 9: ...which are suited to the type of cabinet To install the range hood correctly first fit the 4 screws A and then the 4 screws B in accordance with the diagramin figure4 Afterfixingtherange hood to the lower part of the cabinet place grille D Fig 4 back in the correct position During this procedure make sure that grille D is fastened properly The appliance expels the fumes through an outside wall or a...

Страница 10: ... 10 Fig 5 Fig 4 Fig 3 ...

Страница 11: ...st be 2 wire with ground If the electrical supply does not meet the above requirements call a licensed electrician before proceeding Route house wiring as close to the installation location as possible in the ceiling or back wall Refer to Wiring Locations on page 12 Connect the hood wiring to the house wiring in accordance with local codes Grounding instructions The grounding conductor must be con...

Страница 12: ...er securing it using the screws that were previously removed The appliance should be installed at a minimum height of 27 up to a maximum height of 32 for optimal performance If a connection ductwork composed of two parts is used the upper part must be placed outside the lower part Do not connect the range hood exhaust duct air to the same duct air used to exhaust hot air or fumes from other applia...

Страница 13: ...ards 2 Carbon filter kit XORFK04 The kit includes an air diverter A 2 screws and 2 expan sions plugs B and 2 round filters C To convert this model from the sunction to the filter ing version it is not necessary to use the air deviator A and the screws B DUCTLESS RECIRCULATING OPTION ...

Страница 14: ... 14 Fig 2 The filters C must be applied to the suction unit inside the hood centering them inside of it and turning them 90 until they snap into place Fig 3 Put the aluminum panels back in place Fig 1 ...

Страница 15: ... 15 USE If the apparatus is equipped with the following controls A LIGHT B OFF C SPEED I D SPEED II E SPEED III G MOTOR WORKING indicator ...

Страница 16: ...they have to be replaced If the replacement and washing instructions are not followed the anti grease filters may present a fire hazard The active carbon filters are used to purify the air which is released back into the room The filters are not washable or re usable and must be replaced at least once every four months The active carbon filter saturation level depends on the frequency with which t...

Страница 17: ...ce DO NOT allow deposit to remain for long periods of time DO NOT use ordinary steel wool or steel brushes Small bits of steel may adhere to the surface causing rust DO NOT allow salt solutions disinfectants bleaches or cleaning compounds to remain in contact with stainless steel for extended periods Many of these compounds contain chemicals with may be harmful Rinse with water after exposure and ...

Страница 18: ...ontrolled by a fuse 5x20 mm 125V 5A In case of necessity it can be replaced only by spe cialized personnel Replacing halogen light bulbs To replace the halogen lamps B from the insideofthecookerhoodpressdownwards with two fingers as shown in Fig 9 ...

Страница 19: ... 19 XOI27S ...

Страница 20: ... 20 OPTIONS AND ACCESSORIES Model XORFK04 Ductless Recirculating Filter Kit ...

Страница 21: ... 21 INSTALLATION PREPARATION Check installation hardware Locate the hardware package packed with the hood and check contents Aluminum filter TYPE DESCRIPTION N A 1 8 x 1 2 8 ...

Страница 22: ...oved for dishwasher safe cleaning Unit Dimensions 27 3 4 W x 11 D x 10 T Cut Out Dims 26 7 16 W x 10 1 16 D Mounting Height from cooking surface 27 32 Duct Options and Electrical Requirements 6 inch duct required Ductless Option for applications where no ducting in available AC 120v 60Hz 4 35amp Options Optional recirculating kit if outside venting is unavailable Model XORFK04 XO is Exclusively Di...

Отзывы: