background image

 

 

 

 

Содержание OPTIMA-RT10-06K

Страница 1: ...6K 10K www xmart ups com VER 161205 GA2 ENG 1 VER 1612 05 ENGLISH USER MANUAL OPTIMA RT10 6K 10K UPS ONLINE DOUBLE CONVERSION RACK TOWER INSTALLATION OPTIMA RT10 06K 230V OPTIMA RT10 10K 230V ISOTX 06...

Страница 2: ...or distributed totally or partially without written approval of XMART XMART can introduce modifications in their products or manuals without further notice XMART is not responsible of mistakes or miss...

Страница 3: ...PRODUCT DESCRIPTION 4 INSTALLATION INSTALLATION INDIVIDUAL UPS INSTALLATION PARALLEL UPS 5 OPERATION MODES 6 OPERATION INTERFACE KEYBOARD LCD 7 UPS CONFIGURATION 8 START UP INDIVIDUAL UPS PARALLEL UPS...

Страница 4: ...ere are ALWAYS dangerous voltages EVEN the UPS is OFF and unplugged CAUTION There are dangerous voltages in internal DC Capacitors Wait at least 10 minutes after turning off UPS before opening it to a...

Страница 5: ...netic field immunity IEC EN 61000 4 8 Level 4 PERFORMANCE UPS Part 3 Methods of operation specifications and test requirement IEC EN 62040 3 IT Equipment SAFETY Part 1 General Requirements IEC EN 6095...

Страница 6: ...Ethernet optional card under SNMP protocol This model can be installed in both tower format and inside 19 rack cabinets Rack installation requires some mounting accessories not included with the produ...

Страница 7: ...ectrical shock because high DC voltage External battery banks must be revised before connecting them to UPS to confirm their DC voltage is compatible with this UPS DC polarity of the Battery bank must...

Страница 8: ...find voltage in input lines of the UPS so that a backfeed failure could represent an electrical shock risk for the operator An effective backfeed design must be able to open automatically all UPS AC...

Страница 9: ...in sites exposed to sun light or heat sources Temperature at operation site should never rise over 35 C Batteries life shortens over 25 C Installation site must be dry fresh free of dust fibers and an...

Страница 10: ...net 19 RACK MOUNTING Rack UPS must be installed using L Shape type guides for supporting UPS weight Usually this kind of supports is provided with rack cabinets If not UPS distributor can provide orig...

Страница 11: ...AL OPTIMA RT10 6K 10K www xmart ups com VER 161205 GA2 ENG 11 VERTICAL MOUNTING UPS can be installed in vertical format by using plastic supports Fig 1 2 These supports are included inside the box 2 M...

Страница 12: ...INDEX USER MANUAL OPTIMA RT10 6K 10K www xmart ups com VER 161205 GA2 ENG 12 3 MODULES UPS XBART OPTIONAL ISOTX...

Страница 13: ...PTIMA RT 6K and 10K work with 240VDC battery voltage This voltage is provided by battery packs by connecting 20 batteries 12VDC in series There could be some UPS models working with a different DC vol...

Страница 14: ...PUT 1 x 120Vac N1 100 Watts SEPARE OUTPUTS 2 x 120Vac N2 50 Watts C U 6KVA with ISOTX Output 110 220V Unique Output Capacity 6000VA 5400W Output Voltage 120Vac AC Breaker 80A Curve D Max Nominal Curre...

Страница 15: ...t powered including external batteries UPS XBAT UPS with 220V output generated by UPS inverter This product has 2 basic modules UPS Batteries This UPS can be feed with 220V 240V line L N to generate o...

Страница 16: ...module is an optional accessory not included with the UPS It provides 2 galvanic isolated outputs 120V each UPS output is connected to ISOTX input IMPORTANT When ISOTX is connected total power output...

Страница 17: ...05 GA2 ENG 17 ISOTX OUTPUTS CONFIGURATION ISOTX outputs can be connected in 3 different configurations according to the needs of the application IMPORTANT When 2 x 120V output configuration is selecte...

Страница 18: ...llel connection also allows system can grow in power by adding extra units For working parallel as a parallel system all units must share same AC input and AC output Some control cables must be also c...

Страница 19: ...ndable all output neutral lines are connected directly without breakers It is important neutral lines are connected always since neutral is an important electrical reference for all UPS of the paralle...

Страница 20: ...ird UPS must be connected following same principle IMPORTANT It is recommendable all output neutral lines are connected directly without breakers It is important neutral lines are connected always sin...

Страница 21: ...RTANT It is recommendable all output neutral lines are connected directly without breakers It is important neutral lines are connected always since neutral is an important electrical reference for all...

Страница 22: ...d UPS must be connected following same principle IMPORTANT It is recommendable all output neutral lines are connected directly without breakers It is important neutral lines are connected always since...

Страница 23: ...GA2 ENG 23 CONTROL CABLES CONNECTION DIAGRAM Parallel system requires all UPS share some important control information by parallel control cables There are 2 kind of control cables SHARED CURRENT PAR...

Страница 24: ...t on its terminals If bypass mode is not enable UPS will simply lights its LCD Outputs will keep powered off 2 Bypass mode is adopted as soon as a problem is detected in its internal circuitries 3 Byp...

Страница 25: ...SWITCH In case user decides to install a generic external bypass switch without a safety plate status signal the operator will be responsible of setting UPS in static bypass mode before actuating the...

Страница 26: ...ies but also feeds rectifier input UPS output is generated by inverter BATTERY MODE A Input indicator at bottom left corner A shows Battery voltage since there is no valid AC input detected B Output i...

Страница 27: ...INDEX USER MANUAL OPTIMA RT10 6K 10K www xmart ups com VER 161205 GA2 ENG 27 ERROR FAILURE MODE A When a failure is detected UPS display error code with alert symbol on screen...

Страница 28: ...elease before required time UPS will not turn on ENTER When UPS is in configuration mode this key operates as ENTER OFF ESCAPE UPS TURN OFF Press during 2 seconds to turn UPS off SCAPE When UPS is in...

Страница 29: ...NFORMATION It displays AC output voltage Output frequency in Hz ALARMS ERRORS This section of the LCD displays active alarms and errors providing codes and descriptive symbols This section also shows...

Страница 30: ...5 BYAPSS internal static line active 6 ECO mode active 7 Audible alarm beep muted OUTPUT POWER METER This area displays graphically by a 4 segments bar the power supplied by the UPS 25 Supplied Power...

Страница 31: ...Used as key to navigate or changing parameters value ON ENTER Used as ENTER key to confirm modifications MUTE DOWN Used as key to navigate or changing parameters value AVAILABLE FUNCTIONS UNDER EACH...

Страница 32: ...e of input frequency If ATO is selected output frequency will be set by input frequency read when UPS started by first time from 46 to 54 Hz will set to 50Hz from 56 to 64 Hz will set to 60Hz IMPORTAN...

Страница 33: ...under any condition PAR 03 ENA Enable Bypass allowed in both manual and automatic DIS Disable Automatic Bypass allowed but manual is prohibited Set values with keys 09 MAXIMUM RUNTIME This function s...

Страница 34: ...adjusted ADD for increasing SUB for decreasing Set values with keys LCD CODES AND TEXTS TEXT DESCRIPTION BAT Battery Bater a CF Frequency Converter Function Enable Funci n de Convertidor de Frecuencia...

Страница 35: ...er input lines ON at electrical board by setting Circuit Breaker to ON 3 Put Battery Bank breaker to ON in case UPS has XBAT connected 4 Put AC INPUT Breaker to ON in UPS rear panel 5 LCD of UPS must...

Страница 36: ...ALLEL UPS Check all previous requirements are complied If not do nott try to start ups parallel UPS 1 Check parallel UPS are powered OFF and turned OFF 2 Check all input breakers are in OFF position 3...

Страница 37: ...ry backup of remaining UPS could not be enough to keep system running before reconnecting removed unit External breakers could be activated randomly during operation so system could be tripped 3 There...

Страница 38: ...ep s HIGH TEMPERATURE 1 beep s CHARGER FAILURE 1 beep s UPS BLOCKED as consequence of detecting 3 overloads in less than 30 minutes OR MBS cover REMOVED 1 beep s ALARMS ALARM CODES Battery Disconnecte...

Страница 39: ...VERTER output 14 SHORT CIRCUIT detected at Battery SCR 21 SHORT CIRCUIT detected at inverter output 24 COMMUNICATION CAN error 31 DESBALANCED CURRENT IN PARALLEL SYTEM 36 OVER TEMPERATURE 41 CPU COMMU...

Страница 40: ...OLUCION 01 02 03 04 11 12 13 24 6A 6B 6C 60 63 Turn off and power off UPS Disconnect all equipment connected to UPS Restart UPS with no loads connected to its output If UPS starts up without problems...

Страница 41: ...ogy VRLA and specifications 12VDC and similar capacity in AH BATTERIES QUANTITY This type of UPS is equipped at factory with 20 batteries 12VDC connected in serial for a total of 240VDC This UPS can b...

Страница 42: ...on service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty 6 If product is out o...

Страница 43: ...orts Shared Current 3 AC Input Breaker 10 Parallel Control Ports Parallel Control 4 Connector for Ext Bypass status signal 11 FAN UPS 5 DC connector for external batteries 12 FAN ISOTX optional module...

Страница 44: ...Pack 1 m dulo de Bater as Additional packs Paquetes adicionales Charging Amps Corriente de Carga Charging Voltage Voltaje Cargador RT10 6KVA 230 RT10 10KVA 230 6 000VA 6 000W 10 000VA 10 000W 220Vac s...

Страница 45: ...ed 1 100m over 1 000m La salida se reduce en 1 cada 100m sobre los 1 000msnm Note 4 Bypass mode is prohibited automatically when CF function is activated El modo bypass se anula automaticamente cuando...

Страница 46: ...INDEX USER MANUAL OPTIMA RT10 6K 10K www xmart ups com VER 161205 GA2 ENG 46 NOTAS...

Страница 47: ......

Страница 48: ...USA Headquarters 10540 NW 26th St Doral FL 33172 USA EUROPE Headquarters Ave Can Bordoll 60 Nave 4 Sabadell 08202 Spain Latin America Headquarters Zona Ind San Vicente II C F A11 Maracay Venezuela...

Отзывы: