USER MANUAL - OPTIMA UPS 6K/ 10K (ENGLISH)
______________________________________________________________________________________________________________________
20150610 Tower-Rack 6K-10K ISOTX
- 35
09: BATTERY BACKUP MAXIMUM TIME
LCD
Parameter 3:
000~999:
It sets maximum backup time from
0min to 999min. UPS will turn
OFF to protect batteries when time is reached.
DIS:
IT disables this function and batteries will be used until reaching very low
level.
** WE STRONGLY RECOMMEND TO KEEP FACTORY SET VALUE 990 **
10: PROGRAMMABLE OUTPUTS
LCD
Parameter 3:
It configures programmable outputs according to available
options:
ON:
Programmable outputs are supplied without time restrictions.
OFF:
This option turns programmable outputs OFF.
ATO:
This option allows programmable outputs to turn off when timer value is
reached (or very low voltage level, whatever occurs first).
11: PROGRAMMABLE OUTPUTS CONFIGURATION
LCD
Parameter 2: 001.
Menu for timer setting.
Parameter 3: Shutdown time in minutes.
Timer can be set from 0 to 300 min.
Parameter 2: 002
Menu for minimum battery voltage level setting.
Parameter 3: Shutdown voltage in V.
Minimum voltage can be set from 11.2Vdc - 13.6 Vdc. Programmable outlets
are turned off when minimum voltage value is reached.
12: HOT STAND BY: “NO-BATTERY STARTUP” FUNCTION
LCD
Ajuste
Parameter 2: HS.H
Enable or disable Hot standby function. You may choose following two options
in
Parameter 3
:
YES:
Hot standby function is enabled. It means the UPS is set to restart after AC
recovery even without battery connected.
NO:
Hot standby function is disabled. The UPS is running at normal mode and
can’t restart without battery