USER MANUAL - OPTIMA UPS 6K/ 10K (ENGLISH) 

______________________________________________________________________________________________________________________ 

 

20150610 Tower-Rack 6K-10K ISOTX

 

 - 10 

 

  3.- UPS INSTALLATION: SITE PLANING 

 

 

 

 

 

 

 

 
 

SAFETY INSTRUCTIONS 

 

WARNING: Before revising this section you must read and understand very well section 1 of this manual: “GENERAL 

SAFETY INSTRUCTIONS”. 
 

 

WARNINGS, RECOMMENDATIONS AND LIABILITY LIMITATION 

 

REACH AND LIABILITY LIMITATION: 

The preparation of the site, wiring and all protection devices must be supplied by end 

user and it will not be responsibility neither the UPS distributor nor the UPS technician in charge of the start-up. 
The place will be conditioned be end user or electrical contractor and must fulfill with local normative and directives and UPS 
technical requirements. 
This manual describes minimal conditions and technical requirements with which the site must accomplish. 

Directives and requirements described in this manual, do not pretend to substitute in any way local electrical directives or 
normative. 
In some cases, local directives or regulations might be more exigent than UPS technical requirements described by this 
manual. In that case end user electrical contractor must be sure to comply with all related local electrical regulations and 
directives. 
 

WARNING:

 Power lines must be protected by protection devices against over current (breakers) or leak currents with capacity 

and technology appropriate to effectively accomplish its function. Moreover, installation grounding must be correct. 

WARNING: 

Install the UPS in well ventilated locations and leave room enough between UPS and close objects and structures

 

WARNING: 

Do not connect to UPS equipments or devices that exceed its capacity, this would overload the UPS.

 

WARNING:

 This product has been designed to be used indoors protected from water, direct sun light, dust and extreme 

temperature. 

WARNING

: Do not put any object on the UPS; do not apply any force over UPS. Do not cover UPS ventilation. 

WARNING

: This UPS must be connected to appropriate electrical service according to selected model. Technical specs 

sticker in the UPS shows the UPS power ratings. DO NOT connect this UPS to any of its own power outlets, this could 
damage the unit permanently. 

WARNING:

 Do not connect AC motor based equipments without a careful sizing of the UPS based on inrush current instead of 

average current. Inrush current typical of motor based system could overload this UPS. 

 

 

 

Содержание Optima 6K

Страница 1: ...ENGLISH VER 150610 TOWER AND RACK UPS USER MANUAL DOUBLE CONVERSION UPS...

Страница 2: ...roperty of XMART This manual Information cannot be copied or distributed totally or partially without written approval of XMART XMART can introduce modifications in their products or manuals without f...

Страница 3: ...LINES CONFIGURATION AC TERMINAL BLOCKS EXTERNAL BATTERY CONNECTION 5 UPS INSTALLATION PARALLEL UPS TERMINAL BLOCK GENERAL COMMENTS UPS AC LINES CONNECTION PARALLEL CONTROL CABLES CONNECTION 6 START U...

Страница 4: ...There are dangerous voltages in DC Direct Current Capacitors Please Check Capacitor location in Figure 8 4 1 Wait at least 10 minutes after turning off UPS before opening it to access inside DANGER P...

Страница 5: ...quency Magnetic Field IEC EN 61000 4 8 Level 4 EMS Low Freq Signals IEC EN 61000 2 2 EMS ESD IEC EN 61000 4 2 Level 4 EMS RS IEC EN 61000 4 3 Level 3 EMS EFT IEC EN 61000 4 4 Level 4 EMS SURGE IEC EN...

Страница 6: ...S 6KEX 10KEX ISOTX for RACK UPS is an optional external module can be connected at any moment to the UPS Model Internal Batteries Ext Batt Connector Isolation Transformer 6KEX 10KEX Y Y No 6KEX 10KEX...

Страница 7: ...ypass Switch Interruptor Bypass 3 EPO Emergency Stop Parada Emergencia 10 AC Input Breaker Breaker Entrada AC 4 Share Current for parallel UPS para UPS paralelas 11 FAN ISOTX Ventilaci n para ISOTX 5...

Страница 8: ...tor Bypass 3 EPO Emergency Stop Parada Emergencia 10 AC Input Breaker Breaker Entrada AC 4 Share Current for parallel UPS para UPS paralelas 11 FAN ISOTX Ventilaci n para ISOTX 5 Parallel Port for par...

Страница 9: ...RS 232 2 USB 3 EPO Emergency Power Off 4 Share Current Port for parallel function 5 Parallel Port for parallel function 6 SNMP Intelligent Slot 7 Cooling Fans 8 External Bypass Switch port MBS port 1...

Страница 10: ...technical requirements described by this manual In that case end user electrical contractor must be sure to comply with all related local electrical regulations and directives WARNING Power lines must...

Страница 11: ...ver rise over 35 C Batteries life shortens over 25 C Installation site must be dry fresh free of dust fibers and any other objects conductors or not suspended in the air that could get into the UPS th...

Страница 12: ...ded with rack cabinets If not UPS distributor can provide original telescopic guides as optional accessory Small black handles included with the UPS are only for locking purposes UPS cannot be support...

Страница 13: ...tilation and it will allow service UPS when required Do not put any object on the UPS do not apply any force over UPS Do not cover UPS ventilation ELECTRICAL REQUIREMENTS MANDATORY All Power lines mus...

Страница 14: ...ring min size 8 AWG 10 mm2 ISOTX UNIQUE OUTPUT 1 x 120Vac 100 Watts SEPARE OUTPUTS 2 x 120Vac 50 Watts C U 6KVA con ISOTX Output 110 220V Unique Output Capacity 6000VA 4800W Output Voltage 120Vac AC B...

Страница 15: ...Tower Rack 6K 10K ISOTX 15 LEAK CURRENT PROTECTION In many countries now a day it is legally required to install protections against current leakage to protect human beings in cases of leaks o dischar...

Страница 16: ...plug UPS to AC Line as usually ratings of this kind of outlets are not enough to power 6KVA UPS UPS Input wire must be connected by breaker protected line to electric panel board UPS Input and Output...

Страница 17: ...____________________________________ 20150610 Tower Rack 6K 10K ISOTX 17 ISOTX UPS MODEL CAN BE CONFIGURED IN 3 DIFFERENT MANNERS 1 TWO separate 110Vac isolated outputs Each 50 of total UPS capacity 2...

Страница 18: ...__________________________________________________ 20150610 Tower Rack 6K 10K ISOTX 18 RACK TYPE UPS 6 10K Optional ISOTX Module for RACK UPS 6 10K ISOTX module is optional accessory rack module UPS A...

Страница 19: ...ION PROCEDURE UPS Tower type 1 Check all DC breakers are in OFF position 2 Remove all DC connector covers in UPS and EXBATT cabinets 3 Using appropriate cable supplied with the EXBATT connect UPS with...

Страница 20: ...s kind of outlets are not enough to power 6KVA UPS UPS Input wire must be connected directly to electric panel board UPS INPUT AND OUTPUT CONNECTIONS Connect input and output ground wires to proper pl...

Страница 21: ...PS 6K 10K ENGLISH ______________________________________________________________________________________________________________________ 20150610 Tower Rack 6K 10K ISOTX 21 MODEL 6K 10KEX PARALLEL UPS...

Страница 22: ...6K 10K ENGLISH ______________________________________________________________________________________________________________________ 20150610 Tower Rack 6K 10K ISOTX 22 MODEL 6K 10K ISOTX PARALLEL U...

Страница 23: ...IMA UPS 6K 10K ENGLISH ______________________________________________________________________________________________________________________ 20150610 Tower Rack 6K 10K ISOTX 23 PARALLEL UPS CONTROL W...

Страница 24: ...RE 1 Make sure all equipments connected to UPS are off 2 Power AC input at electrical panel board by setting input AC Lines Circuit Breaker to ON 3 Put Battery Bank breaker to ON Only for Ex Models If...

Страница 25: ...by activation of Emergency Switch which must be Normally Closed type in order to guarantee that UPS will shut down when circuit opens 5 Check Maintenance Bypass Switch MBS located in UPS rear panel is...

Страница 26: ...f LCD 12 All UPS will go to NORMAL Online mode at same time 13 Before setting to ON all external output breakers please revise AC voltage output on each UPS Please measure AC output voltage using a di...

Страница 27: ...ks as ESCAPE key when LCD is in configuration menu mode TEST UP BATTERY TEST By selecting TEST key UPS enters into battery test mode during 10s UP It Works as UP key when LCD is in configuration menu...

Страница 28: ...alarms error icons 2 ELAPSED TIMER When UPS switches to battery mode elapsed time during battery mode is displayed in Hours Minutes Seconds 3 ERROR ALARM CODE In case of alarm or error 2 digits code...

Страница 29: ...with AC Line directly If under this mode UPS detects AC input is out of acceptable range it enters into Normal Online mode If an AC failure occurs under ECO mode the UPS s inverter starts working drai...

Страница 30: ...d by inverter FREQUENCY CONVERTER FUNCTION CF CF function enable to generate output frequency as selected IMPORTANT NOTE When CF is activated bypass mode is automatically disable and maximum power out...

Страница 31: ...have their own external protections to allow total electrical isolation 6 There must be enough physical room to allow comfortable access to all UPS of the system Note if any of the above requirements...

Страница 32: ...isable 6 Voltage Range for ECO mode 7 Frequency Range ECO mode 8 BYPASS mode 9 Battery Backup Security Time 10 Programmable Output note 1 11 Programmable Output Settings note 1 11 NO Battery startup f...

Страница 33: ...Automatic Under this mode output frequency is selected according to input frequency 50Hz if input is 46Hz y 54Hz and 60Hz if input is 56Hz y 64Hz ATO mode is factory default value Parameter 3 Frequenc...

Страница 34: ...before trying to enable it If ECO mode is disable next programs 06 and 07 don t need to be configured 06 ECO MODE Input Voltage Range LCD Parameter 2 Sets acceptable low voltage limit Parameter 3 Set...

Страница 35: ...tputs OFF ATO This option allows programmable outputs to turn off when timer value is reached or very low voltage level whatever occurs first 11 PROGRAMMABLE OUTPUTS CONFIGURATION LCD Parameter 2 001...

Страница 36: ...IS FACTORY SET VALUE 14 BATTERY CHARGER ADJUSTMENT LCD Parameter 2 Select Add or Sub for adjusting battery charger voltage Add or Reduce Parameter 3 available adjustment value is from 0V a 9 9V Factor...

Страница 37: ...it 24 Inverter Relay Short Circuit 28 Battery connection problem BATT FAULT 35 Parallel Communication problem 36 UPS Output Short Circuit 41 HIGH Temperature 42 CPU communication problem 43 UPS Output...

Страница 38: ...re Batteries and charger must be inspected by qualified personnel Code 28 Active Continuous beep Very low voltage at batteries or charger failure Batteries and charger must be inspected by qualified p...

Страница 39: ...te Ext Charging Amps Corriente de Carga Charging Voltage Voltaje Cargador 2 0 A Max 273 0 VDC 96 92 EX ISO 90 86 EX ISO 88 84 EX ISO Depending on external battery configuration depende de cantidad de...

Страница 40: ...ador de aislamiento con salida dual 2 x 110Vac Rack 6K 10K UPS Battery 3rd optional cab for ISOTX Rack 6K 10K UPS Bater as 3er por opci n Transf ISO opcional Specifications may change without further...

Страница 41: ...ndling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty 6 If product is out of warranty a reparation proposal will be sent to t...

Отзывы: