USER MANUAL
- OPTIMA-31 10K / 20K / 30K
www.xmart-ups.com
150615-OPT-31 10K/20K/30K (ENGLISH) - 3
2.- AVAILABLE MODELS
OPTIMA-31 10K / 20K / 30K
UPS 3 phases IN (380V L-L & 220V L-N) & 1 phase OUT (220V L-N) for 380/220V systems.
This kind of UPS includes electronic and internal batteries in same UPS cabinet.
This UPS offers 2 kind of outputs:
Output 1: L1-N1: This is the standard UPS output. It can provide 100% of the total capacity in watts of the UPS. In
battery mode this output is powered until UPS shutdowns because energy of the batteries has been drained.
Output 2: L2-N2: This is a programmable output able to provide 100% of total UPS capacity. This output can be
configured to power off automatically in battery mode by reaching a programmable timer. In this way non critical
equipments connected to output 2 can be disconnected when timer limit is reached leaving battery energy available for
critical loads connected to output 1. Programmable function of output 2 is disable in factory settings. It must be enable
if required. When programmable function is disable output 2 operates in same manner than output 1.
OPTIMA-31 10K-NB / 20K-NB / 30K-NB
UPS 3 phases IN (380V L-L & 220V L-N) & 1 phase OUT (220V L-N) for 380/220V systems.
UPS cabinet only includes electronic parts. Batteries must be external.
Output 1: L1-N1: This is the standard UPS output. It can provide 100% of the total capacity in watts of the UPS. In
battery mode this output is powered until UPS shutdowns because energy of the batteries has been drained.
Output 2: L2-N2: This is a programmable output able to provide 100% of total UPS capacity. This output can be
configured to power off automatically in battery mode by reaching a programmable timer. In this way non critical
equipments connected to output 2 can be disconnected when timer limit is reached leaving battery energy available for
critical loads connected to output 1. Programmable function of output 2 is disable in factory settings. It must be enable
if required. When programmable function is disable output 2 operates in same manner than output 1.
EXBATT BATTERY CABINETS
If external batteries are required for 230/120V models or for extending runtime, EXBATT external batteries can be connected
directly to the UPS.
EXBATT-33-T10K:
EXBATT for OPTIMA-31 10K. Includes 20 batteries 12V/9AH with DC breaker 50Amps.
DC voltage: 240Vdc (nominal).
EXBATT-33-T20K:
EXBATT for OPTIMA-31 20K. Includes 40 batteries 12V/9AH with DC breaker 100Amps.
DC voltage: 240Vdc (nominal).
EXBATT-33-T30K:
EXBATT for OPTIMA-31 30K. Includes 60 batteries 12V/9AH with DC breaker 150Amps.
DC voltage: 240Vdc (nominal).
WARNING
External battery packs for OPTIMA-31 models could be not compatible with some other OPTIMA UPS models.
Make sure you will connect compatible external battery pack to your UPS to avoid permanent damages not covered by
warranty.