TOWER UPS INSTALLATION
SITE CONSIDERATIONS
* This product has been designed to be used indoors, protected from water, direct sun light, dust and extreme temperature.
* Install the UPS in well ventilated location or air conditioned room. Temperature must be always in acceptable range according to technical
specifications table of this manual. It is strongly recommendable controlled room temperature between 21ºC to 24ºC for longer battery and UPS
life.
* There must be minimum 1 meter free room distance between UPS and any wall or object. It will allow better ventilation and it will allow
service UPS when required.
* Do not put any object on the UPS; do not apply any force over UPS. Do not cover UPS ventilation.
ELECTRICAL REQUIREMENTS (MANDATORY)
* All Power lines must be protected by magneto-thermal protection devices against over current (breakers) with capacity and technology
appropriate to effectively accomplish its function as indicated in this manual. Moreover, installation grounding must be correct.
* This UPS must be connected to appropriate electrical service according to selected model. Technical specs sticker in the UPS shows the UPS
power ratings. DO NOT connect this UPS to any of its own power outlets, this could damage the unit permanently.
* If external battery cabinets are connected to UPS, it is necessary to install one DC breaker between UPS and each external battery cabinet.
Original External Battery cabinets normally include its own input breaker.
LEAK CURRENT PROTECTION
In many countries, now a day, it is legally required to install protections against current leakage to protect human beings in cases of leaks o
discharges to ground. It is responsibility of the end user and/or electrical contractor selecting and including these protection devices in the
electrical circuit of the UPS.