HOOD SERVICE PROCEDURES
Allen Bradley Power Flex 4M Restoring XLT Defaults
Q
Read the entire instruction before programming.
TIP
To reset VFD settings change Pl 12 to 1. The VFD will reset to factory default settings. To cycle
power, tum circuit breaker off and on and the HMC will load the factory parameters into the VFD.
Pl05=65
Pl06=2
Pl08=4
Pll0=2
A451=9
A452=60
T201=2
T202=6
A404=60
Maximum Frequency
Start Source
Speed Reference
Decel Time
Auto Reset Tries
Auto Reset Delay
Terminal Block Group
(I/0)
Terminal 5
Terminal Block Group
(I/0)
Terminal 6
Jog Frequency
Test run the motor by turning on one of the oven/hood buttons located on the HUI.
Power �
Complete VFD manual available at
www.xltovens.com
.
Technical Support US: 888-443-2751
S
i
mple
.
Smart.
Technical Support INTL: 316-943-2751