Operation of Xintex Propane Fume Detector(s) 
 
There are 3 LEDs located on the Display Unit for each channel on the system, as well as an LED for 
the Solenoid Valve status.  The Green LED, located at the top, indicates that the system is 
operational.  The Yellow LED, located in the center, indicates that there is a Fault in the system.  
This is to notify the user to check the connections and wire runs of the sensors.  There may be a 
break in the wiring or a disconnected sensor on that channel.  The Red LED, located at the bottom, 
indicates a fume buildup of 20% of the LEL (Lower Explosive Limit) which is considered an alarm.  
The alarm horn will sound when the Red LED is illuminated.

 

The alarm horn will actuate, Solenoid 

Valve will close, and the Solenoid Valve status LED will deactivate when the Red LED is 
illuminated.  Whenever the Solenoid Valve status LED is illuminated, the Solenoid Valve is open. 
 

The alarm status will continue as long as the fume level remains at an elevated level.  The alarm 
horn may be silenced by 

pressing the “Check/Reset” button

.  The alarm will reactivate after 30 

seconds as long as the Detector remains in alarm status.  The problem should never be considered 
corrected as long as the Red LED is illuminated.   
 
 
 
 
 
 
 
 
 
 
 

P2BS-S01-D 

P1BR-S01-D 
P1CR-S01-D 
 

Содержание P-1BS-R

Страница 1: ...ol 24V Solenoid P 1CS R Chrome Round Solenoid Control 12V Solenoid P 1CS 24 R Chrome Round Solenoid Control 24V Solenoid Dual Channel System P 2BS R Black Square Solenoid Control 12V Solenoid P 2BS 24...

Страница 2: ...talling the Display Unit P1BR S01 D P1CR S01 D P2BS S01D 6 Installing the Solenoid Valve for LPG Applications 6 Routing Sensor Cable s FS X01 CABLE XX 6 Installing Propane Fume Sensor s FS T01 7 Elect...

Страница 3: ...e system Specification System Specifications P 1BS R P 1CS R Operating Voltage 9 18V DC Nominal Current Draw 55mA 12V DC Maximum Current Draw 725mA 9V DC Operating Temperature 40 F 40 C to 185 F 85 C...

Страница 4: ...e bottom indicates a fume buildup of 20 of the LEL Lower Explosive Limit which is considered an alarm The alarm horn will sound when the Red LED is illuminated The alarm horn will actuate Solenoid Val...

Страница 5: ...er 2A May be obtained Display Unit 2A fuse recommended Solenoid Valve YELLOW Switching Ground 2A Fuse Included FS X01 CABLE XX FS T01 FS X01 CABLE XX FS T01 P2BS S01 D RED Power 1 0 Amp Fuse from Circ...

Страница 6: ...ctical The tank itself should be mounted outside the cabin or crew quarters to avoid the possibility of gas accumulation due to a leak NOTE TIGHTEN TO 12 13 FT LBS DO NOT OVER TIGHTEN NOTE ALL PIPING...

Страница 7: ...used Yellow 16 GA wire is provided for connecting the Display Unit to the Solenoid Valve Connect the Yellow wire to the Solenoid Valve Connect the positive voltage to the Solenoid Valve NOTE UNITS MAN...

Страница 8: ...ngers and crew exit the passenger compartment and vessel if possible Ventilate the space being monitored Carefully check all fuel lines and other potential sources of propane fume leaks If leaks are i...

Страница 9: ...ent of Fireboy Xintex LLC does not assume the costs of removal and or installation of the product or any other incidental costs of removal and or installation of the product or any other incidental co...

Отзывы: