Electrical Connections (G1BR-B01-D/G1CR-B01-D or G2BS-B01-D) 

 

The Display Unit operates on 9-30

 

VDC.  A Red and a Black 16 GA wire are provided for 

connecting to the power source.  Connect the Red wire to Power (+) with an inline 1.0 
Amp fuse.  Connect the Black wire to Ground (-).  
 
A 2A fused Yellow 16 GA wire is provided for connecting the Display Unit to the Bilge 
Blower system.  Connect the Yellow wire to terminal 86 of MB30RLY.  Connect the 
+12/24 VDC to terminals 30, 85, and the Manual Blower Switch.  Connect the Ground to 
the Blower System.  
 

NOTE 

UNITS MANUFACTURED PRIOR TO JANRUARY 01, 2018 DO NOT INCLUDE THE 2A FUSE.  A 
DEDICATED 2A FUSE OR BREAKER SHOULD BE USED TO POWER THE BILGE BLOWER SYSTEM. 

 

NOTE 

IMPROPER CONNECTIONS WILL DAMAGE THE DISPLAY UNIT AND WILL VOID WARRANTY. 

 

Testing the System Operation 
 
The Gasoline Fume Detectors can be tested by pressing the “Check/Reset” button on the face of 
the Display Unit.  The Display Unit will cycle through the LEDs and the alarm horn will activate 
while the LEDs cycle.   
 
Unplug the Gasoline Fume Sensor from each channel of the Detection System one at a time.  The 
Yellow “Fault” LED should illuminate.  If the Yellow LED does not illuminate, remove Display Unit 
and return direct to manufacturer following the instructions at the back of this manual. 
 
Press the Blower button on the Display Unit.  The Blower system should turn on until the button is 
released. 
 
Testing the Gasoline Fume Sensors 
 

WARNING 

DO NOT USE A GASOLINE SOAKED RAG OR A PARTIALLY FULL CONTAINER OF GASOLINE TO TEST A 
SENSOR.  THE RAW GASOLINE COULD IGNITE, RESULTING IN SERIOUS INJURY.   
 
Test the Sensors by holding an unlit Butane lighter to the sensor.  Within a few seconds, the Red 
“Danger” LED should illuminate, Blower will activate, and the alarm horn will sound.  Remove the 
lighter from the Sensor and mute the alarm horn.  After approximately one minute, the Red LED 
will shut off. 
 
 
 

Содержание G-1BB-R

Страница 1: ...nnel Systems G 1BB R Black Round Blower Control G 1CB R Chrome Round Blower Control Dual Channel System G 2BB R Black Square Blower Control Owner s Manual Installation Instructions Read and comply with all instructions warnings and limitations before installing servicing or removing this device ...

Страница 2: ...ine Fume Detector s 4 Installation 7 Installing the Display Unit G1BR B01 D G1CR B01 D or G2BS B01 D 7 Routing Sensor Cable s FS X01 CABLE XX 7 Installing Gasoline Fume Sensor s FS T01 7 Electrical Connections G1BR B01 D G1CR B01 D or G2BS B01 D 8 Testing the System Operation 8 Testing the Gasoline Fume Sensors 8 Maintenance 9 In the Event of an Alarm 9 Repairing Xintex Gasoline Detection Componen...

Страница 3: ...dition these units automatically actuate your bilge Blower to purge the space of fumes The systems use sensors located in a place of interest and a central display unit that notifies you of the state of the system Specification System Specifications G 1BB R G 1CB R Operating Voltage 9 30 VDC Nominal Current Draw 55mA 12 VDC Maximum Current Draw 95mA 9 VDC Maximum Blower Output Current 2A Operating...

Страница 4: ...l The Red LED located at the bottom indicates a fume buildup of 20 of the LEL Lower Explosive Limit which is considered an alarm The Blower status LED and alarm horn will actuate when the Red LED is illuminated Whenever the Blower status LED is illuminated the Blower is active The alarm status will continue as long as the fume level remains at an elevated level The alarm horn may be silenced by pr...

Страница 5: ...ound Blower Switch YELLOW Switching Ground 2A Fuse Included 12 VDC from Blower Circuit Breaker MB30RLY 30 86 87 85 G1BR B01 D G1CR B01 D FS X01 CABLE XX FS T01 RED Power 1 0 Amp Fuse from Circuit Breaker BLACK Ground Blower Ground YELLOW Switching Ground 2A Fuse Included 12 VDC from Blower Circuit Breaker MB30RLY 30 86 87 85 Blower Switch ...

Страница 6: ...ume Sensor Connect to the Display Unit using the attached quick disconnect connectors Take care not to pinch break or cut the Sensor Cable or put too much stress on the connectors while routing the cable Secure the Sensor Cable with the appropriate hardware for the application NOTE DO NOT CUT EXTENSION CABLE FOR ANY PURPOSE DOING SO VOIDS THE PRODUCTS WARRANTY LONGER CABLES ARE AVAILABLE FROM 20 F...

Страница 7: ...tors can be tested by pressing the Check Reset button on the face of the Display Unit The Display Unit will cycle through the LEDs and the alarm horn will activate while the LEDs cycle Unplug the Gasoline Fume Sensor from each channel of the Detection System one at a time The Yellow Fault LED should illuminate If the Yellow LED does not illuminate remove Display Unit and return direct to manufactu...

Страница 8: ...y and make any necessary repairs Repairing Xintex Gasoline Fume Detection Components Xintex Gasoline Fume Detection Components are not field serviceable Components must be returned to the factory for any repairs Returning Xintex Gasoline Detection Components No product may be returned for credit or repair without a written Returned Material Authorization RMA form Purchaser must call or email Fireb...

Страница 9: ...ment of Fireboy Xintex LLC does not assume the costs of removal and or installation of the product or any other incidental costs of removal and or installation of the product or any other incidental costs which may arise as a result of any defect in material or workmanship and e upon discovery of defect Buyer shall immediately cease use of and notify Fireboy Xintex LLC Any warranty implied by law ...

Отзывы: