18141, H, 01/28/2020

 

 

Electrical Connections (G1BR-B01-D/G1CR-B01-D or G2BS-B01-D) 
 
The Display Unit operates on 9-30V DC.  A Red and a Black 16 GA wire are provided for connecting 
to the power source.  Connect the Red wire to Power (+) with an inline 1.0 Amp fuse.  Connect the 
Black wire to Ground (-).  
 
A 2A fused Yellow 16 GA wire is provided for connecting the Display Unit to the Bilge Blower 
system.  Connect the Yellow wire to terminal 85 of MB30RLY/MB30RLY-24.  Connect the positive 
(+) voltage to terminals 30, 86, and the Manual Blower Switch.  Connect the Ground to the Blower 
System.  

 

NOTE 

UNITS MANUFACTURED PRIOR TO JANUARY 01, 2018 DO NOT INCLUDE THE 2A FUSE.  A 
DEDICATED 2A FUSE OR BREAKER SHOULD BE USED TO POWER THE BILGE BLOWER SYSTEM. 

 

NOTE 

IMPROPER CONNECTIONS WILL DAMAGE THE DISPLAY UNIT AND WILL VOID WARRANTY. 

 

Testing the System Operation 
 
The Gasoline Fume Detectors can be tested by pressing the 

Check/Reset

 button on the face of 

the Display Unit.  The Display Unit will cycle through the LEDs and the alarm horn will activate 
while the LEDs cycle.   
 
Unplug the Gasoline Fume Sensor from each channel of the Detection System one at a time.  The 

Yellow “Fault” LED should illuminate.  If the Yellow LED does not illuminate, remove Display Unit 

and return direct to manufacturer following the instructions at the back of this manual. 
 
Press the Blower button on the Display Unit.  The Blower system should turn on until the button is 
released. 
 
Testing the Gasoline Fume Sensors 
 

WARNING 

DO NOT USE A GASOLINE SOAKED RAG OR A PARTIALLY FULL CONTAINER OF GASOLINE TO TEST A 
SENSOR.  THE RAW GASOLINE COULD IGNITE, RESULTING IN SERIOUS INJURY.   
 
Test the Sensors by holding an unlit Butane lighter to the sensor.  Within a few seconds, the Red 

“Danger” LED should illuminate

, Blower will activate, and the alarm horn will sound.  Remove the 

lighter from the Sensor and mute the alarm horn.  After approximately one minute, the Red LED 
will shut off. 
 
 
 

Содержание G-1BB-24-R

Страница 1: ...24V Solenoid G 1CB R Chrome Round Blower Control 12V Solenoid G 1CB 24 R Chrome Round Blower Control 24V Solenoid Dual Channel System G 2BB R Black Square Blower Control 12V Solenoid G 2BB 24 R Black...

Страница 2: ...4 Installation 6 Installing the Display Unit G1BR B01 D G1CR B01 D or G2BS B01 D 6 Routing Sensor Cable s FS X01 CABLE XX 6 Installing Gasoline Fume Sensor s FS T01 6 Electrical Connections G1BR B01...

Страница 3: ...tem Specifications G 1BB R G 1CB R Operating Voltage 9 30V DC Nominal Current Draw 55mA 12V DC Maximum Current Draw 95mA 9V DC Maximum Blower Output Current 2A Operating Temperature 40 F 40 C to 185 F...

Страница 4: ...The Red LED located at the bottom indicates a fume buildup of 20 of the LEL Lower Explosive Limit which is considered an alarm The Blower status LED and alarm horn will actuate when the Red LED is il...

Страница 5: ...Switch YELLOW Switching Ground 2A Fuse Included Positive voltage from Blower Circuit Breaker MB30RLY 30 85 87 86 G1BR B01 D G1CR B01 D FS X01 CABLE XX FS T01 RED Power 1 0 Amp Fuse from Circuit Break...

Страница 6: ...of the Gasoline Fume Sensor Connect to the Display Unit using the attached quick disconnect connectors Take care not to pinch break or cut the Sensor Cable or put too much stress on the connectors whi...

Страница 7: ...e Detectors can be tested by pressing the Check Reset button on the face of the Display Unit The Display Unit will cycle through the LEDs and the alarm horn will activate while the LEDs cycle Unplug t...

Страница 8: ...and make any necessary repairs Repairing Xintex Gasoline Fume Detection Components Xintex Gasoline Fume Detection Components are not field serviceable Components must be returned to the factory for a...

Страница 9: ...ent of Fireboy Xintex LLC does not assume the costs of removal and or installation of the product or any other incidental costs of removal and or installation of the product or any other incidental co...

Отзывы: