XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Connecting Mains to the Power Supply PCB
The panel’s PSU combines the functions of a power supply unit, battery charging unit, battery
monitoring unit and earth fault monitoring unit. It should be positioned in the panel’s enclosure as
shown in Fig. 3 below. DO NOT operate the panel without the Power Supply PCB correctly mounted in
the enclosure with its three PCB retaining screws securely tightened.
CAUTION: DO NOT CONNECT MAINS TO THE POWER SUPPLY PCB UNTIL THE INSTALLATION IS
COMPLETE AND ALL RELEVANT PCBS ARE CORRECTLY ATTACHED WITHIN THE PANEL.
XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 7 of 36
Fig. 3 : Power Supply PCB layout and Mains connection (Full Protective Cover & Cable Cover shown fitted)
C
C
C
C
C
C
C
C
C
C
C
C
C
C
ON
O
ON
ON
O
ON
ON
ON
ON
N1
N1
N1
N1
N1
N1
N1
N1
N
N
N
N
N
N
N
N
N
L
L
L
L
L
L
CONN2
BLK
-
RED+
VR1
F2
F1.6A
PL2
PL1
F
F
F1
F
F
1A
1A
2
2
50V
50V
0V
50V
50V
50V
V
H
H
H
RC
RC
C
RC
C
C
RC
F1
F
F
F
VVV
HRC
FF1
1A
2
0
50
250
00V
V
0V
VVVV
HRC
V
0
VV
0
HR
R
V V
0V
1
A
250
R
1A
R
THIS WAY UP
CONN1
N
L
Mains Input (CONN1)
L = Live (BROWN)
N = Neutral (BLUE)
= Earth (GREEN/YELLOW)
The incoming Mains earth wire
MUST
be
connected to the terminal marked
and
NOT
to the base earth distribution
post.
Exposed live parts under cable
cover. Isolate first, then remove
the small cable cover by
loosening its single retaining screw which
is retained in the cover. Only operate the
PSU with this cover securely fitted.
Connector Cable Socket (PL1)
Connect other end of lead to
the rear of Main Control PCB.
WHEN THE RED ‘HAZARDOUS
VOLTAGES PRESENT’ LED IS LIT
HAZARDOUS VOLTAGES ARE
PRESENT. ALLOW TO DISCHARGE FOR AT
LEAST 5 MINUTES BEFORE REMOVAL &
HANDLING.
Incoming Mains Cable
This cable
MUST
be segregated from
other cables. Good quality cable
glands
MUST
always be fitted.
Battery Connector
(CONN2)
(Leads supplied in the
panel’s accessory
pack.) See page 11 for
connection details.
PSU Earth Distribution Strap
This strap
MUST
be
connected to the spade
on the base earth
distribution post before
operation.
Battery Fuse (F2)
Primary Fuse (F1)
Exposed Live
parts under fuse
cover. Isolate
before removal.
CABLE
COVER
REMOVED