PREINSTALLATION
Environmental and electrical requirements
This section provides important environmental and electrical
requirements for your LPS that must be accommodated.
4050
Environmental and electrical requirements for the 4050 LPS are
provided in table 1-15 and 1-16.
Table 1-15.
Environmental requirements
Operating temperature
Normal: 68° F to 76° F/20° C to 24° C
Minimum: 60° F/16° C
Maximum: 80° F/27° C
Humidity
Normal: 45 +/- 10%
Minimum: 30%
Maximum: 60%
Heat dissipation, online
Operating:
15,000 BTU per hour
Standby:
7,500 BTU per hour
Heat dissipation, offline
Operating:
15,500 BTU per hour
Standby:
8,000 BTU per hour
Table 1-16.
Electrical requirements
System controller
120/208 or 120/240 VAC; 50/60 Hz,
30 amp service, NEMA L14-30R
1.5 KVA both in standby mode and when
operating
Note: Magnetic tape unit assumed
(maximum draw)
Printer
U.S./Canada, 60 Hz: 120/208 or 120/240
VAC; 30 amp service, NEMA 14-30R
.875 KVA in standby, 3.1 when operating
International, 50 Hz:
220/240 VAC or 380 VAC
Agency certification
UL, CSA, IEC