Modules produce the most power when they are pointed directly at the sun. For installations where the Solar 
Modules are attached to a permanent structure, the Modules should be tilted for optimum winter 
performance. As a rule, if the system power production is adequate in winter, it will be satisfactory during the 
rest of the year. The module tilt angle is measured between the solar Modules and the ground. Optimal tilting 
of module is almost the same as the latitude of installation location. 

 
 
 
 
 

RECOMENDED TILT ANGLES FOR A FIXED SYSTEM

 

SITE LATITUDE IN DEGREES

 

FIXED TILT ANGLE

 

0° to 15° 

15° 

15°to 25° 

SAME AS LATITUDE 

25°to 30° 

LA5° 

30° to 35° 

LA10° 

35°to 40° 

LA15° 

40° + 

LA20° 

 

MOUNTING OF THE MODULES  

CLIPS LOCATION 

XDISC S.A. recommends using typical aluminium clips designed for framed modules.  

ASOL-250P-WSR module mounting configurations must meet the following requirements: 

-

 

Clearance of 7mm or more between modules is required to allow for thermal expansion.  

-

 

Modules must not be subjected to wind or snow loads in excess of the maximum permissible loads and 
must not be subjected to excessive forces due to thermal expansion of the support structure. 

Содержание ASOL-250P-WSR

Страница 1: ...MOUNTING INSTRUCTION for PHOTOVOLTAIC MODULES Type ASOL 250P WSR ...

Страница 2: ...UNDING 6 ELECTRICAL SPECIFICATIONS 6 By pass diode specifications 6 LOCATION SELECTION 6 MODULE TILT ANGLE 6 MOUNTING OF THE MODULES 7 Clips location 7 Mounting with screws 9 MAINTENANCE OF PHOTOVOLTAIC MODULES ASOL 250P WSR 9 Periodic cleaning of the module 9 Visual inspection 9 Connection and wiring controls 10 Manufacturer 10 ...

Страница 3: ...d professional manner Electrical work should be performed by a qualified electrician WARNING This photovoltaic module produces electricity when exposed to the sun or other light sources The electrical hazard from the voltage and current of a single module is low However the voltage increases as modules are connected in series and the available current increases as modules are connected in parallel...

Страница 4: ...uch the terminals with bare hands Use insulated tools when wiring to solar module terminals wear rubber gloves to eliminate shock or burn potential when wiring solar modules Regardless of whether you are working on a new or existing roof never allow the sheathing and metal parts to become wet Protect the sheathing and metal parts from rain during the installation Failure to do so may cause leaks W...

Страница 5: ...for components capacity of conductors size of fuses and size of control systems connected to the module output are determined multiply the values of short circuit current Isc and open circuit voltage Voc that are marked in ASOL 250P WSR series modules by the coefficient 1 25 Before installing your system contact local authorities to determine the necessary permit installation and inspection requir...

Страница 6: ...st Conditions rated power Accordingly when determining component ratings and capacities the module short circuit current at STC should be multiplied by 1 25 and a correction factor should be applied for the open circuit voltage An additional 1 25 multiplier for the short circuit current for a total of 1 56 for sizing conductors and fuses may be applicable depending on your local regulations BY PAS...

Страница 7: ... location RECOMENDED TILT ANGLES FOR A FIXED SYSTEM SITE LATITUDE IN DEGREES FIXED TILT ANGLE 0 to 15 15 15 to 25 SAME AS LATITUDE 25 to 30 LATITUDE 5 30 to 35 LATITUDE 10 35 to 40 LATITUDE 15 40 LATITUDE 20 MOUNTING OF THE MODULES CLIPS LOCATION XDISC S A recommends using typical aluminium clips designed for framed modules ASOL 250P WSR module mounting configurations must meet the following requi...

Страница 8: ...e mounted and must not cause any twist or stress to be placed on the module Modules should be secured to mounting structure using four aluminium at least 80 mm long module clips The retaining clips must each provide a minimum contact area of 10 mm x 80 mm The centre of mounting clips must be located on the long side of the module between 350 mm and 400 mm from the edge See following figure for all...

Страница 9: ...d on the transparent cover of the module reduces its performance and can produce reverse effects similar to those produced by shading The problem can become serious in the case of industrial waste or waste caused by birds The intensity of the effects depends on the opaqueness of the residue The layers of dust that reduce the intensity of the sun are not dangerous and the reduction in power is not ...

Страница 10: ... wiring Also check to be sure that mounting hardware is tight Loose connections will result in damage for array Do not touch live parts of cables and connectors Use appropriate safety equipment insulated tools insulating gloves etc when touching them Cover the front surface of the Module by an opaque or other material when repairing The ASOL 250P WSR modules when exposed to sunlight generate high ...