Pre-Installation
Before installing the XW Inverter/Charger, read all instructions and cautionary markings
located in this manual.
Location
The XW Inverter/Charger is certified for indoor (heated or unheated) installations only.
Close to battery
bank
Locate the inverter as close to the batteries as possible in order to keep the battery cable
length short. The maximum recommended battery cable length is 10 feet (3 m).
Locate any electronic equipment susceptible to radio frequency and electromagnetic
interference as far away from the inverter as possible.
Fire safety
Do not locate the inverter near readily flammable materials such as cloth, paper, straw, or
plastic sheeting. Flammable materials should be kept a minimum distance of 24 inches
(60 cm) from the top surface and 12 inches (30 cm) from either side surface and the front
of the XW Inverter/Charger.
Knockout Preparation and Air Filter Installation
Remove your choice of knockouts from the chassis to facilitate conduit installation for
wire runs. Ensure no debris from this procedure remains inside the inverter enclosure.
Important:
Be sure to obtain the appropriate permits, if necessary, prior to starting this
installation.
Installations must meet all local codes and standards.
Installations of this equipment
should only be performed by skilled personnel such as qualified electricians and Certified
Renewable Energy (RE) System installers.
WARNING: Personal Injury
The XW Inverter/Charger weighs approximately 120 pounds (54 kg). To prevent personal injury,
always use proper lifting techniques and have someone assist with lifting during installation.
WARNING: Explosion and Corrosion Hazard
Do not locate the inverter directly above the batteries or in the same compartment as vented
batteries.
Important:
Do not drill, cut, or punch holes into the XW power distribution Panel. Use only the
knockouts provided for conduit entry.
Figure 2-1
Air Filter and AUX Connector Installation
Air Filter
Tuck the air filter
into the grooves
in the sides of the
air vent cover.
If planning on using the Aux
Port features, insert the AUX
Connector into the Aux Port.
See “AUX Port” on page 2–24
for wiring details.
AUX Connector
Содержание XW4024-120/240-60, XW4548-120/240-60, XW6048-120/240-60
Страница 2: ......
Страница 3: ...XW Power System Installation Guide...
Страница 16: ...xvi...
Страница 24: ...1 8...
Страница 70: ...2 46...
Страница 71: ...Basic Functional Test Multiple Inverters 975 0239 01 01 2 47 This manual for use by qualified personnel only...
Страница 72: ...Inverter Charger Installation 2 48 975 0239 01 01 This manual for use by qualified personnel only...
Страница 73: ...Basic Functional Test Multiple Inverters 975 0239 01 01 2 49 This manual for use by qualified personnel only...
Страница 74: ...Inverter Charger Installation 2 50 975 0239 01 01 This manual for use by qualified personnel only...
Страница 118: ...5 20...
Страница 128: ...B 2...
Страница 142: ...C 8...
Страница 145: ......