Alternate System Configurations
C–6
975-0239-01-01
This manual for use by qualified personnel only
Generator Wiring to the Inverter
WARNING: Shock Hazard
Before making any electrical connections, ensure both the AC and DC disconnect devices are in
the OPEN (disconnect) position.
Important: If the load is too big for the inverter to operate from battery power, do not install the
load in the inverter powered electrical panel.
Figure C-5
Generator Wiring directly to the Inverter
Torque all inverter terminal block
connections to 25 inch-pounds.
This illustrates an example only. Actual
wiring requirements may vary.