Remote Operation
Remote Monitoring of Output Voltage and Current
78
Operating Manual for XFR 2.8kW Series Power Supply
Remote Monitoring of Output Voltage and Current
Readback
Signals
The J2 connector on the rear panel provides access to calibrated readback signals for
remote monitoring of the output voltage and current. Rear panel switches SW1-5 and
SW1-6 allow you to select either a 0-5 Vdc or a 0-10 Vdc range for the output. The
readback signal represents 0 to 100% of the power supply’s output.
See Table 4.3 for the required J2 connections and switch settings for remote
monitoring of readback signals with 0-5 Vdc or 0-10 Vdc outputs. Use shielded pair
wiring (20 to 24 AWG) and ground the shield to J10 sense connector terminal 1
(return sense) or to the chassis.
Table 4.3
Power Supply Settings for Remote Monitoring of Readback Signals
Note:Check the readback accuracy any time you reset switches SW1-5 and SW1-6.
See Section 5. Calibration.
Readback Signal
J2 Connection
Signal (+)
J2 Connection
Return (–)
Switch SW1 Setting
Output Voltage
(0-5 Vdc)
J2-10
J2-9
SW1-5 OFF (OPEN)
Output Voltage
(0-10 Vdc)
J2-10
J2-9
SW1-5 ON (CLOSED)
Output Current
(0-5 Vdc)
J2-12
J2-11
SW1-6 OFF (OPEN)
Output Current
(0-10 Vdc)
J2-12
J2-11
SW1-6 ON (CLOSED)
Содержание XFR 2800
Страница 2: ......
Страница 3: ...Operating Manual for XFR 2800 Watt Series Programmable DC Power Supply...
Страница 14: ...List of Figures xii Operating Manual for XFR 2 8kW Series Power Supply...
Страница 16: ...List of Tables xiv Operating Manual for XFR 2 8kW Series Power Supply...
Страница 88: ...Calibration Calibrating for Readback Accuracy 86 Operating Manual for XFR 2 8kW Series Power Supply...
Страница 89: ......