10-amp Charging Profile

Table A-6 provides the specific charging parameters for the 10 Charging 
Profile.

0-amp Charging Profile

When Charger Setting 0 A is selected, the Battery Charger is disabled and 
will not charge the batteries. Use this mode if other DC charging sources 
are available or if it is necessary to temporarily disconnect the AC 
charging system.

Table A-6

10-amp Charging Profile

Parameter Name

Default Value

Charger Setting

10 A

Maximum Bypass Current

1200 W (10 A) 

Bulk Mode

10 A

Absorption Mode

14.2 Vdc (4 hours maximum)

Float Mode

13.7 Vdc (8 hours)

Switches from Absorption to 
Float Mode

4 A

Switches from Float Mode 
back to Bulk Mode within the 
8-hour limit, if the Float 
current increases to 6 A.

6 A

Standby Mode (Off Mode)

12.5 Vdc

Estimated charging time

32 hours based on a single battery box with 
two 100 Ah, 12 Vdc batteries and no other DC 
charging sources

975-0289-01-01(PowerHub_1800).book  Page 6  Friday, January 5, 2007  12:47 PM

Содержание PowerHub 1800

Страница 1: ...PowerHub 1800 Installation Guide PH1800 975 0289 01 01 PowerHub_1800 book Page 1 Friday January 5 2007 12 47 PM...

Страница 2: ...975 0289 01 01 PowerHub_1800 book Page 2 Friday January 5 2007 12 47 PM...

Страница 3: ...PowerHub 1800 Installation Guide 975 0289 01 01 PowerHub_1800 book Page i Friday January 5 2007 12 47 PM...

Страница 4: ...IN WRITING XANTREX TECHNOLOGY INC XANTREX A MAKES NO WARRANTY AS TO THE ACCURACY SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION B ASSU...

Страница 5: ...e who needs to plan for and install the PowerHub 1800 Permanent installations should be done by certified technicians or electricians Installers should have adequate knowledge of national and local el...

Страница 6: ...gs identify conditions or practices that could result in personal injury or loss of life CAUTION Cautions identify conditions or practices that could result in damage to the unit or other equipment Im...

Страница 7: ...that are intended for use with this product Doing otherwise may result in a risk of fire electric shock or injury to persons 5 To avoid a risk of fire and electric shock make sure that all of the ins...

Страница 8: ...rvice the PowerHub yourself may result in a risk of electrical shock or fire and will void your warranty Internal capacitors remain charged after all power is disconnected 8 The PowerHub must be provi...

Страница 9: ...ion follow these instructions and those published by the battery manufacturer 6 Make sure that nothing is blocking the air vents on the back of the enclosure 7 Never smoke or allow a spark or flame ne...

Страница 10: ...ipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful...

Страница 11: ...er or an experienced radio TV technician for help Power Down Procedure If softwired To Power Down the PowerHub 1800 Figure ii Power Down Procedure for Softwired Installations Disconnect Loads Press ON...

Страница 12: ...5 Disconnect any loads directly connected to the front panel of the PowerHub Press ON OFF Switch to turn OFF Inverter Charger Disconnect the Utility power by opening the AC input circuit breaker in t...

Страница 13: ...olar Applications 1 7 Wind Applications 1 8 Combination Applications 1 9 2 Planning Planning Overview 2 2 Tools Required 2 3 Hardware Materials Required 2 3 Environmental Requirements 2 3 Dimensions 2...

Страница 14: ...ound Fault Protection Renewable Energy Solar Array Maximum 1000 W 3 16 DC Wiring Renewable Energy Wind Maximum 1000 W 3 17 Replacing the Top Cover 3 18 Double check 3 18 Power Up Procedure 3 19 Power...

Страница 15: ...Cabling for Two Batteries 3 5 Figure 3 5 Connecting the Battery Bank to the Inverter 3 6 Figure 3 6 Connecting Two Battery Boxes to the Inverter 3 7 Figure 3 7 Replacing the Top to the Battery Box 3 8...

Страница 16: ...ftwired Installations 3 21 Figure 3 21 Power Down Procedure for Hardwired Installations 3 22 Figure 3 22 Replacing Ground Fault Protection Fuse 3 24 Figure A 1 Three Stage Charging Process A 4 975 028...

Страница 17: ...ecifications for the Inverter A 2 Table A 2 Electrical Specifications for the Battery Box A 2 Table A 3 Physical Specifications of the Inverter A 3 Table A 4 Physical Specifications of the Battery Box...

Страница 18: ...ii 975 0289 01 01 PowerHub_1800 book Page ii Friday January 5 2007 12 47 PM...

Страница 19: ...1 Introduction Chapter 1 describes the features and functions of the PowerHub 1800 Figure 1 1 The PowerHub 1800 975 0289 01 01 PowerHub_1800 book Page 1 Friday January 5 2007 12 47 PM...

Страница 20: ...eries when an AC source generator or utility grid is available Run time on batteries will vary depending on the size of the loads using the power Figure 1 2 PowerHub 1800 Components PowerHub 1800 Inst...

Страница 21: ...he Battery Box one on each side Two pairs of DC input terminals for renewable energy connections one 32 A input terminal and one 80 A input terminal External inputs to these terminals must be external...

Страница 22: ...lar and wind renewable energy inputs a 32 A and an 80 A See Figure 3 9 on page 3 10 for a detailed illustration of the Input Output and ground terminals Regulatory This system complies with CSA 107 1...

Страница 23: ...generators in non permanent installations For fixed permanent installations Xantrex recommends using electrical code compliant wiring methods Important The total amount of output power available to po...

Страница 24: ...knowledge of national and local code to ensure the installation passes inspection by the local electric authority Figure 1 5 Hardwired Utility Applications Example only Actual installation may vary Im...

Страница 25: ...lectrical codes Installers should have adequate knowledge of national and local code to ensure the installation passes inspection by the local electric authority Figure 1 6 Hardwired Solar Application...

Страница 26: ...s Installers should have adequate knowledge of national and local code to ensure the installation passes inspection by the local electric authority Figure 1 7 Hardwired Wind Applications Wind Turbine...

Страница 27: ...ection by the local electric authority Figure 1 8 Hardwired Combination Applications Wind Turbine Must be self regulated DC IN AC OUT AC IN AC Distribution Panel Sub Panel Solar Panel s and Charge Con...

Страница 28: ...1 10 975 0289 01 01 PowerHub_1800 book Page 10 Friday January 5 2007 12 47 PM...

Страница 29: ...2 Planning Chapter 2 contains information on planning the installation of this equipment 975 0289 01 01 PowerHub_1800 book Page 1 Friday January 5 2007 12 47 PM...

Страница 30: ...provided with all the equipment 6 Review all material provided with the batteries 7 Review any material related to the installation of the renewable energy components 8 Collect all necessary tools an...

Страница 31: ...to be determined by the location of the installation See Table 3 1 on page 3 11 Conduits and appropriate fittings for wire runs e g wire nuts Breaker panels 15 A circuit breakers and appropriately siz...

Страница 32: ...eave adequate space for access if the unit is to be hardwired 12 may not be adequate IMPORTANT The Powerhub should be mounted on concrete floors or on floors designed to support a minimum load of 100...

Страница 33: ...mum dimension of battery to be 12 W 6 75 D 9 H including terminal posts Terminal Location Top required Terminal Type L type or screw in terminal Important The PowerHub 1800 is designed to be permanent...

Страница 34: ...ormance and charging anomalies can occur if types sizes or age of batteries are not identical CAUTION Keep the weight of the batteries in mind when installing dual battery boxes Ensure the structure f...

Страница 35: ...nd may vary based on model brand of appliance Run Time PowerHub 2 battery boxesc hours c Operating times assume a fully charged 400 Ah battery bank and may vary based on model brand of appliance Cordl...

Страница 36: ...oltaic solar panels that meet the following requirements 12 V solar panels up to 400 W maximum on 32 A DC input terminal or 1000 W maximum on 80 A DC input terminal Solar panels require additional equ...

Страница 37: ...___________________________ __________________________________________________________ __________________________________________________________ ______________________________________________________...

Страница 38: ...2 10 975 0289 01 01 PowerHub_1800 book Page 10 Friday January 5 2007 12 47 PM...

Страница 39: ...nents if used 4 Connect the battery bank to the inverter 5 Connect the DC sources if used 6 Connect the AC sources a if hardwired close utility input breaker or b if softwired plug AC cord into genera...

Страница 40: ...on which side of the inverter box the Battery Box will be placed and locate the four 6 32 mounting screws on that side s of the inverter These screws can be identified by the small ring of bare metal...

Страница 41: ...he screw interlocks with the top of the keyhole slot inside the Battery Box Also ensure that the washers on the mounting screws end up on the inside of the battery box and not between the battery box...

Страница 42: ...nverter If using one battery These cables are connected to the Anderson Plugs in the front panel of the battery box If using two batteries see Figure 3 6 for additional cabling instructions Split Wash...

Страница 43: ...portant When disconnecting batteries ensure all incoming power has been disconnected Then remove the Positive red cable FIRST and the negative black cable LAST CONNECT SECOND Positive red Cable from t...

Страница 44: ...e check the cabling of the batteries to ensure proper polarity BEFORE connecting the battery box to the inverter Damage caused to the inverter due to improper battery cabling is not covered by the lim...

Страница 45: ...h the Anderson connectors from the second Battery box over the top of the fuses in the front of the second battery box 5 If the unit is going to be softwired connect the Anderson cables to the inverte...

Страница 46: ...Phillips screws in the plastic bag provided to secure the top in place Torque to 1 3 nm 11 5 in lb 2 Align the screw holes from the top to the enclosure Repeat this procedure for the second battery b...

Страница 47: ...ended to allow connection to portable generators in non permanent installations For fixed permanent installations Xantrex recommends using electrical code compliant wiring methods See Permanent Wiring...

Страница 48: ...Remove the 5 6 32 Phillips screws on the top of the inverter Lift off the panel to expose the terminals Wiring Terminals Enlargement BEFORE REMOVING INVERTER COVER Check to ensure the AC Indicator LED...

Страница 49: ...used Manufacturer s recommendation 20 3 Nm 180 in lbs DC Input 80 A DC Input 100 A fused Manufacturer s recommendation 20 3 Nm 180 in lbs DC Ground Manufacturer s recommendation 20 3 Nm 180 in lbs Sys...

Страница 50: ...rgy Sources IMPORTANT Be sure to install approved conduit and strain relief in the knockout holes to protect the wiring from being damaged by any sharp edges along the hole openings If installing AC f...

Страница 51: ...e one Connect the PowerHub to a 15 A circuit breaker in the AC Distribution Panel This AC Distribution Panel may not be fed with any other AC sources Torque Neutral and Line terminals to 1 3 nm 11 5 i...

Страница 52: ...l to 1 8 nm 16 0 in lbs Connect the PowerHub to a 15 A circuit breaker in the AC Distribution Panel This AC Distribution Panel may not be fed with any other AC sources Torque Neutral and Line terminal...

Страница 53: ...quirements Be sure to consult your local electric authority for additional requirements Figure 3 14 Connecting the DC Input Renewable Energy Solar Panel Example only Actual installation may vary Torqu...

Страница 54: ...lectric authority for additional requirements Figure 3 15 Connecting the DC Input Renewable Energy Solar Array Example only Actual installation may vary Example only Consult the PV Manufacturer for sp...

Страница 55: ...nal requirements Figure 3 16 Connecting the DC Input Renewable Energy Wind Example only Actual installation may vary Torque Positive Negative and Ground terminals to 20 3 nm 180 in lbs IMPORTANT Wind...

Страница 56: ...the solar panels wired properly Are the wind generators cabled properly Are the appropriate disconnects circuit breakers etc in place Is all the wiring and cabling in undamaged condition Figure 3 17...

Страница 57: ...dure for Softwired Installations Connect the Loads Press ON OFF Switch to turn ON Inverter Charger Connect the PowerHub to the generator and turn the generator ON if required Connect the Battery Box e...

Страница 58: ...Input Open Inverter Output breaker Apply DC Input power by closing the DC Disconnect Input Breaker or disconnect from the Renewable Energy inputs Apply Utility power if available from the Main AC Dist...

Страница 59: ...Power Down Procedure for Softwired Installations Disconnect Loads Press ON OFF Switch to turn OFF Inverter Charger Disconnect the PowerHub from the generator and turn the generator OFF Disconnect the...

Страница 60: ...3 6 4 5 Disconnect any loads directly connected to the front panel of the PowerHub Press ON OFF Switch to turn OFF Inverter Charger Disconnect the Utility power by opening the AC input circuit breake...

Страница 61: ...tection Fuse The ground fault protection fuse will blow when severe leakage occurs between the PV array and earth ground or when the system has been installed with faulty DC wiring Before replacing th...

Страница 62: ...ted 1A 250 Vac slow blow or equivalent 4 Replace the panel on the top of the inverter and tighten all five screws securely Figure 3 22 Replacing Ground Fault Protection Fuse Remove the 5 6 32 Phillips...

Страница 63: ...A Specifications Appendix A provides electrical and physical specifications for the PowerHub 1800 975 0289 01 01 PowerHub_1800 book Page 1 Friday January 5 2007 12 47 PM...

Страница 64: ...ac Low Battery Cutout 10 5 Vdc with 240 W load and 11 0 V with 240 W load High Battery Cutout 15 0 Vdc Transfer Relay Rating 20 A Transfer Time AC to Inverter 40 ms AC Qualification Time 20 seconds Pr...

Страница 65: ...orption Stage the constant voltage mode is limited to 14 2 Vdc The current will drop as batteries voltage rises Upon dropping to 4 A the unit will transition to the Float charge This stage will not ex...

Страница 66: ...oltage drops below 12 5 Vdc the unit will start a new Bulk stage Figure A 1 Three Stage Charging Process Voltage Bulk Stage Absorption Stage Float Stage Standby Stop Mode Current Maximum Charge Amps S...

Страница 67: ...500 W 4 A Bulk Mode 40 A Absorption Mode 14 2 Vdc 4 hours maximum Float Mode 13 7 Vdc 8 hours Switches from Absorption to Float Mode 4 A Switches from Float Mode back to Bulk Mode within the 8 hour l...

Страница 68: ...em Table A 6 10 amp Charging Profile Parameter Name Default Value Charger Setting 10 A Maximum Bypass Current 1200 W 10 A Bulk Mode 10 A Absorption Mode 14 2 Vdc 4 hours maximum Float Mode 13 7 Vdc 8...

Страница 69: ...ion 2 3 F Factory installed AC Cord 3 11 FCC information to the user viii first aid viii Function 1 2 G ground fault protection 3 23 Ground Terminals 1 4 H Hardware 2 3 Hardwired Permanent Application...

Страница 70: ...2 975 0289 01 01 PowerHub_1800 book Page 2 Friday January 5 2007 12 47 PM...

Страница 71: ...975 0289 01 01 PowerHub_1800 book Page 3 Friday January 5 2007 12 47 PM...

Страница 72: ...oll free NA 1 360 925 5097 Tel direct 1 800 994 7828 Fax toll free NA 1 360 925 5143 Fax direct customerservice xantrex com www xantrex com 975 0289 01 01 Printed in China 975 0289 01 01 PowerHub_1800...

Отзывы: