Power Down Procedure
975-0289-01-01
3–23
If hardwired......
To Power Down the PowerHub 1800:
WARNING
ELECTRIC SHOCK HAZARD
Physically disconnect DC input sources (solar or wind) to ensure that DC power is OFF.
Failure to follow these instructions can result in death or serious injury.
Figure 3-21
Power Down Procedure for Hardwired Installations
1
2
3
6
4
5
Disconnect any loads directly
connected to the front panel of
the PowerHub
Press ON/OFF
Switch to turn OFF
Inverter/Charger
Disconnect the Utility
power by opening the AC
input circuit breaker in the
main panel.
Disconnect the Battery Box(es)
from the Inverter
Disconnect Loads connected to
the PowerHub through AC
Distribution Panel (Sub-panel)
by opening the Inverter Output
Circuit Breaker.
Disconnect the
DC Input.(s)
975-0289-01-01(PowerHub_1800_IG).book Page 23 Thursday, June 4, 2015 9:49 AM