64
Freedom SW Owner’s Guide
Configuring the Freedom SW using the SCP
ACIn Settings
The
ACIn Settings
menu configures the voltage and
frequency limits for AC Input quantification range. These are
the limits at which the Freedom SW considers input voltage
qualified—that is, suitable for charging batteries or powering
loads. If the input voltage is not qualified according to these
settings, the Freedom SW transfers from using AC input to
inverting.
Figure 30
ACIn Settings Menu Screen
Table 14
Setting Defaults and Ranges
Model
Freedom SW 2012 / 3012
Freedom SW 2024 / 3024
Item
Default
Min
Max
Default
Min
Max
AC1 Breaker
30A
5A
30A
30A
5A
30A
AC1 Lo Volt
95V
78V
115V
95V
78V
115V
AC1 Hi Volt
135V
125V
140V
135V
125V
140V
AC1 Lo Freq
55Hz
44Hz
59Hz
55Hz
44Hz
59Hz
AC1 Hi Freq
65Hz
61Hz
70Hz
65Hz
61Hz
70Hz
FSW3012 00: ACIn Settings
ACIn Breaker
ACIn Lo Volt
ACIn Hi Volt
ACIn Lo Freq
ACIn Hi Freq
[30A]
[95V]
[135V]
[55Hz]
[65Hz]