Freedom Sequence Intelligent Power Manager Installation Guide
Installing the Freedom Sequence
Step 3: Connecting the AC Relay Wires
8
mm
AC relay wires
N
G
L
AC
Cable
(1)
Strip the phase and neutral wires of the AC cable to be used for the AC relays as shown above.
If the ground wire is jacketed instead of bare, strip it as well as shown above.
(2)
Open the AC
relay terminal’s cage clamp using a 3.5mm blade long neck screwdriver by inserting the tip
through the square hole.
N G L
15A
(3)
Starting with one end of an AC cable, connect each wire into a corresponding terminal on one
of the circuit breakers on the main AC panel.
NOTE
: The AC cable must be compatible with the
ratings of the circuit breaker to which it will be connected.
(4)
On the other end of the AC cable,
insert each wire into its corresponding cage clamp slot in the power manager’s AC relay terminal.
Once the wires have been properly inserted, close the cage clamp by removing the screwdriver.
(5)
Tug the wires (soft-pull test) to make sure they are firmly in place. Correct any loosened
connections.