38

   

  •

 Testing for backfeed. If a backfeed

condition is indicated, disconnect from
shorepower and disconnect the AC output
wires from the inverter. Make sure the inverter
is OFF.

Caution: 

Apply shorepower and measure for

voltage between the black and white wires that
were attached to the inverter output feeding the
electrical panel or loads, not the inverter output
wires. If there is voltage on these wires, a
backfeed condition exists and must be
corrected or damage will result.

3. Test the battery charger function:

    

 • 

With shorepower applied and the

transfer switch engaged, the battery charger
should be in operation. The CHARGE LED will
blink for 8 seconds. After the 8 seconds, the
unit will enter the charge mode and the LED
will be illuminated.  (When using Temperature
Sensitive Charging, this time may be longer.)

       When AC is available, the unit will auto-
matically default to charge mode without the
operator setting the unit in CHARGE mode. It is
necessary to press the CHARGE switch OFF,
if you do not want to charge.

Verify the charger is working by using a

volt meter. Use this same method on the start
or auxiliary battery connected to the echo-
charge to verify echo-charge operation. The
battery voltage should gradually increase.
If using a Remote Control Panel, DC Amps
LED indicates charger output and the DC Volts
LED indicates an increase in battery voltage.

Note: 

The house battery bank must be  above

13.0 volts for the echo-charge to be  operational.

INSTALLATION CHECKS

     

• 

Turn the inverter ON—the green LED

should blink. Remove shorepower and the
inverter should automatically pick up the AC
load when shorepower is removed.

Repeat the test for transfer and battery

charger with the generator if you have one.

Congratulations, you have completed a

successful installation.

Note: 

For low power system shutdown

mode, both the INVERT and CHARGE LEDs
must be OFF.

Содержание Freedom Marine Series

Страница 1: ...Xantrex Freedom Marine Series Inverter Charger Owner s Manual Freedom Marine 10 15 20 25 30...

Страница 2: ...e battery charging and automatic AC transfer switching For your convenience service is available world wide from qualified service centers If you have any questions about your Freedom Marine Inverter...

Страница 3: ...n Precautions 21 Installation 22 Key Installation Points Grounding Neutral Bonding AC Wiring AC Input AC Output Ground Fault Circuit Interrupters Remote Control Wiring TSC Temperature Sensor DC Wiring...

Страница 4: ...ng loads larger than the continuous rating of the inverter INTRODUCTION The internal transfer switch allows the Freedom Inverter Charger to be connected to an external AC source and transfer the sourc...

Страница 5: ...al echo charge is current limited to 15 amps and follows the three stage charge curve of the inverter charger and battery setting of the house battery bank The number of active echo charge outputs dep...

Страница 6: ...present Response from idle is instantaneous When using a Freedom or Link remote control panel the idle threshold is adjustable The unit does not produce 120 volts when in idle An idle pulse is sent ou...

Страница 7: ...led based on battery temperature The charger adjusts the charge voltage to the best level insuring safe charging for selected battery type Charge voltage regulation optimizes the battery life cycle TH...

Страница 8: ...control panel or Link instrument When operating the inverter charger with out a Freedom or Link remote control panel Front Panel Controls and Indicators INVERT MODE The INVERT push button switch is lo...

Страница 9: ...VERLOAD Red LEDs When both LEDs are blinking an AC backfeed was detected A backfeed occurs when AC power from an external source is connected to the output of the inverter Inspect wiring for a possibl...

Страница 10: ...ne active echo charge output Freedom 25 30 have two active outputs The echo charge automatically switches On Off charging an auxiliary or start battery without affecting the main house battery bank Th...

Страница 11: ...eshold Battery Type and Battery Capacity Advanced Remote Control Panels Link Instruments Advanced remote control panels are also available the Link 1000 2000 and 2000 R LINK 1000 Link 1000 controls th...

Страница 12: ...t of charging and will experience some water loss It is very important that the electrolyte level be checked frequently and topped off with distilled water when necessary Follow the battery manufactur...

Страница 13: ...o gel cell batteries The charge parameters are similar to wet cell batteries Battery Selection The most important feature to consider in making your battery selection is to select true deep cycle batt...

Страница 14: ...visable to connect batteries of different case sizes or amp hour ratings in the same battery bank Always use properly sized wire and terminals for your interconnecting battery cables For size informat...

Страница 15: ...s and brands of appliances may vary If using the same battery bank for the inverter and other DC loads be sure to consider the power consumption of the DC loads when sizing the battery bank n o i t p...

Страница 16: ...ct high voltage charging that gasses these batteries is harmful to them They typically require a lower bulk charge voltage Gel cell batteries require a higher float voltage than wet cell bat teries Co...

Страница 17: ...nance Use of the Remote Control Panel or Link Instrument provides the ability to periodically apply an equalizing charge Refer to Remote Control Panel or the Link Instrument Owner s Manual for more in...

Страница 18: ...nce charge voltage limit When it reaches the float voltage set point the float charge stage is engaged The float charge stage holds the battery voltage constant at a preset voltage level where it is s...

Страница 19: ...he same specific gravity 3 Mixing up of the electrolyte Electrolyte in battery cells tends to separate into layers of acid and water The vigorous bubbling action of the battery during equalizing serve...

Страница 20: ...3 1 2 4 1 6 3 1 1 4 1 1 3 1 0 8 7 2 2 4 1 3 3 1 0 4 1 5 3 1 3 4 1 7 3 1 2 4 1 2 3 1 0 7 1 2 4 4 1 5 3 1 1 4 1 6 3 1 4 4 1 8 3 1 3 4 1 3 3 1 0 6 6 1 6 4 1 7 3 1 3 4 1 8 3 1 5 4 1 9 3 1 4 4 1 4 3 1 0 5...

Страница 21: ...s Needed Flathead and Phillips Screwdrivers Wrench for connecting battery cables 9 16 Wire Cutters Wire Strippers Misc assorted wire ties and connectors Accessories Needed for Installation Before begi...

Страница 22: ...n Boat and Yacht Council ABYC recommendation A 25 Refer to page 33 INSTALLATION 5 Do not connect the inverter battery negative cable to the vessel safety ground Run the negative cable directly to the...

Страница 23: ...ways use proper wire and connectors The proper battery cable size is critical Consult ABYC UL NEC or your marine electrician for recommended battery cable size Considerable amperage flows in the DC ci...

Страница 24: ...assis grounding wire Refer to local and national electrical codes Note For additional information on grounding refer to American Boat and Yacht Council ABYC recommendation A 25 6 Refer to page 33 INST...

Страница 25: ...service supplies the inverter charger additional 20 ampere 15 ampere in Canada maximum branch circuit INSTALLATION rated breakers will be required between the inverter charger AC output and the loads...

Страница 26: ...n branch circuits must be equipped with a Ground Fault Circuit Interrupter GFCI Consult the code or a qualified marine electrician for details Any such branch circuits must be protected by a branch ci...

Страница 27: ...he accessory package before continuing the installation The negative cable should be connected directly to the negative post of the house or auxiliary battery bank or the ground side of a current shun...

Страница 28: ...72 inches of the battery or within 7 inches of a positive bus or switch Recommended Fuse UL Listed Class T JLLN with a DC Rating This fuse with fuse holder is available from your dealer or Xantrex Fo...

Страница 29: ...20 Dual Input Dual Output Freedom Marine Model 25 and 30 Can be connected with single in single out mode Can be connected with dual in single out mode Can be connected with dual in dual out mode l a...

Страница 30: ...power is applied to both the AC Out 1 and AC Out 2 outputs Charger Transfer Mode 1 With power applied to AC In 1 only the Charger is on and power from AC In 1 is transferred to both AC outputs Power...

Страница 31: ...e inverter or rapidly discharging the battery bank To avoid the need for this manual form of energy management installation options 2 3 or 4 should be considered If a generator is installed in the sys...

Страница 32: ...ischarging the battery bank and eliminates the need to manually manage the energy usage of these loads when using inverter power The inverter AC input must be supplied power from a 30 amp breaker in t...

Страница 33: ...ower or generator power from the main panel This split load approach will help avoid problems such as overloading the inverter or rapidly discharging the battery bank and eliminates the need to manual...

Страница 34: ...Single Output 30 Amp Transfer Separate Charge Input Power Sharing Not Active AC ground and DC ground are shown connected therefore galvanic protection is recommended Always consult Local and National...

Страница 35: ...ld remain connected to the Main AC Panel These loads are only supplied by shorepower or generator power from the main panel This split load approach will help avoid problems such as overloading the in...

Страница 36: ...C ground and DC ground are shown connected therefore galvanic protection is recommended 2 Neutral buses are required if Shore Power is supplied from two Separate 30A sources Always consult Local and N...

Страница 37: ...ltage The DC Amps LED will not be lit be cause the unit is in the idle mode Add a load of 7 watts or more to the output of the inverter A 40 watt incandescent light bulb will work fine The DC Amps LED...

Страница 38: ...e the unit will auto matically default to charge mode without the operator setting the unit in CHARGE mode It is necessary to press the CHARGE switch OFF if you do not want to charge Verify the charge...

Страница 39: ...i n r a W n a h t e r o m r o 0 1 n a h t s s e l s t l o v 5 1 n e e r G d i l o S n e e r G g n i k n i l B d e R d i l o S o n t u b y d a e r r e g r a h C g n i t r e v n I r e v O e l b a l i a...

Страница 40: ...e t t a b r e t r a t s e h t d n a y r e t t a b e s u o h e h t n e e w t e b e c n e r e f f i d l l i w e g r a h c o h c e e h t s t l o v 2 3 n a h t r e t a e r g s i e c n e r e f f i d f I r...

Страница 41: ...sorbed Glass Mat Battery A lead acid maintenance free battery AWG American Wire Gauge A standard used to measure the size of wire GLOSSARY Circuit An electric circuit is the path of an electric curren...

Страница 42: ...A 02269 9101 617 770 3000 Negative Designating or pertaining to electrical potential The negative terminal is the point from which electrons flow during discharge Ohm A unit for measuring electrical r...

Страница 43: ...V y r e t t a B r e d n U r e v O e g a t l o V y r e t t a B r e d n U r e v O e g a t l o V y r e t t a B r e d n U r e v O e g a t l o V y r e t t a B r e d n U r e v O t i u c r i c t r o h S t i...

Страница 44: ...tly at Phone 1 800 670 0707 toll free in North America 1 604 422 2777 direct Fax 1 604 420 2145 Email CustomerService xantrex com Direct returns may be performed according to the Xantrex Return Materi...

Страница 45: ...tates and provinces do not allow limitations or exclusions on implied warranties or on the duration of an implied warranty or on the limitation or exclusion of incidental or consequential damages so t...

Страница 46: ...hone number where you can be reached during work hours A brief description of the problem 3 Ship the unit prepaid to the address provided by your Xantrex customer service representative If you are ret...

Страница 47: ...47...

Страница 48: ...Xantrex Technology Inc Toll free 1 800 670 0707 Direct 1 604 422 2777 Fax 1 604 420 2145 CustomerService xantrex com www xantrex com 445 0194 01 01 Rev 2 Printed in the U S A...

Отзывы: