2–2
975-0468-01-01
Electrical Specifications: Inverter Mode
DC Input
Low operating voltage range
“
SdL
” setting
10.5–15.5 V
High operating voltage range
“
SdH
” setting
11.8–15.5 V
Under voltage alarm/shutdown
Under voltage recovery
“
SdL
” setting
10.5/11.0 V
12.0 V
Under voltage alarm/shutdown
Under voltage recovery
“
SdH
” setting
11.8/12.3 V
12.6 V
Safe non-operating voltage range
0–16 Vdc
Normal voltage
12.5V
Nominal current at full load
100A
AC Output
Output voltage
120 Vac
Continuous power
1.0kW @ 25 °C
Surge power
17A
(2kW for 200 ms)
Max short-circuit current
55A peak
Frequency
60 Hz
Wave shape
Modified Sinewave
Power derating above 40 °C ambient
temp
See “Invert Power Derating vs.
Ambient Temperature” on
page 2–6.
Peak efficiency
≥
88%
Full load efficiency
≥
85%
Other
No load input power (producing
output voltage)
≤
10W
Off mode current draw
≤
3mA