manualshive.com logo in svg
background image

http://www.xantrex.com

Freedom e-GEN System Installation Guide for OEM Installers

975-1027-01-01 Rev A

Jan 2021

Copyright © 2021 Xantrex LLC. All Rights Reserved.

All trademarks are owned by Xantrex LLC and its affiliates.

3

6

Arc Flash Energy Specifications

Table 4

below quantifies the hazard level of arc flash energy that each battery system is capable of

producing. Calculations are based on NFPA 70E D.5.1 using the Maximum Power Method applied for a
maximum of six modules in parallel connection.

Configuration

V

sys

Impedance mΩ

Ibf, calc.

I

arc

IEm cal/cm

2

3x IEm cal/cm

2

Distance where

IEm=1.2 (Arc

Boundary), inches.

Hazard level

GT12V450

12.8

0.34

37833

18916

0.082

0.246

4

0

GT12V525

12.8

0.3

43390

21695

0.094

0.282

5

0

GT12V600

12.8

0.35

36398

18199

0.079

0.236

4

0

GTX12V630

12.8

2.31

5541

2771

0.012

1.036

2

1

GT24V300

25.6

0.32

80000

40000

0.346

1.039

9

0

GT48V150

48

0.9

53432

26716

0.434

1.301

10

0

GT51V150

51.2

0.85

60117

30059

0.52

1.561

11

0

Formula:

I

arc

= 0.5 × Ibf

IEm = 0.01 × V

sys

 ×  I

arc

 × *T

arc

 ÷ D

2

(Arc Flash Energy)

T

arc

= 70ms fuse clearing time

Table 4 Hazard level of arc flash energy

Category

Energy level

Typical PPE examples

0

n/a

non-melting, flammable materials (e.g. untreated cotton, wool, rayon, etc.)

1

5 cal/cm

2

Fire resistant (FR) shirt and fire resistant (FR) pants

2

8 cal/cm

2

Cotton und FR shirt and FR pants

3

25 cal/cm

2

Cotton und FR shirt and FR pants + FR coverall

4

40 cal/cm

2

Cotton und FR shirt and FR pants + double layer switching coat and pants

Table 5 Hazard/risk classification per NFPA 70E-2018

5

DC Cable and Fuse Requirements

WARNING

HAZARD OF ELECTRIC SHOCK, FIRE, OR PERSONAL INJURY

Equipment shall only be installed and serviced by qualified electrical personnel who have training,
knowledge, and experience in installing electrical equipment and applying applicable installation codes.

Failure to follow these instructions can result in death or serious injury.

IMPORTANT

l

The following table contains the minimum system DC cable size requirements for
single-insulated copper conductors rated 75 °C in free air based on ambient
temperature of 30 °C according to NEC 2017 Table 310.15(B)(17). This table does
not apply to conductors in raceway or conduit, or in ambient above 30 °C.

Device*

Typical Amps (A)

Cable Size (AWG)**

Alternator

270

4/0

Freedom XC PRO Inverter/Charger

320

4/0

BMS

300

4/0

Chassis battery

90

2

* cable is from the Device to the DC busbar
** free air, 30 °C ambient

Table 3 Minimum system DC cable size requirements

l

Use DC cables with a higher insulation temperature rating (105 °C) if possible.
However, a higher insulation temperature rating does not mean the conductor size
can be reduced due to the temperature ratings of the terminal connections. Always
use a qualified installer to ensure conductor sizing complies with regional, national,
and local electrical codes.

l

The DC cables must be UL marked and certified.

l

Longer cables may cause excessive voltage drop and affect system performance.
Keep cable length as short as practically possible.

l

Use twin wires [pos(+) and neg(-) DC cables] for all DC connections. Do not use the
vehicle chassis in place of the DC negative connection. The system requires reliable
DC return paths.

l

The battery system must be used with a Xantrex-approved fuse (see

Table 1

for a list

of approved fuse options). The main battery fuse and all other fuses in the system
must be installed on the positive (ungrounded) conductor as close to their power
sources as possible. Distance restrictions may apply according to applicable codes.

l

The DC load branch, if installed, must be properly fused. The total DC load branch
should not exceed 30A to avoid overheating the main DC cables and blowing the
main battery fuse. It is the installer's responsibility to ensure the voltage, current and
interrupt ratings of the DC load branch fuse are adequate to protect the cables and
downstream loads according to applicable codes.

l

Use Xantrex-approved busbars (Blue Sea, 2104) to make the DC interconnections to
ensure sufficient current-carrying capacity. You must follow the connection order at
the busbar terminal studs (DC load - alternator - BMS - Freedom SW) as shown in the
system diagram for optimal heat transfer. Use the same connection order for both
positive and negative busbars.

l

Ensure there is sufficient space between the DC positive and negative busbars and
fuse holders.

l

All terminals must be tightened according to the manufacturer’s torque specifications.

l

Certain codes require a service disconnect such as a battery disconnect switch. In
this case, you must select a battery disconnect switch with a continuous current rating
of no less than 450A and a voltage rating of no less than 12V.

l

Ensure all system devices are properly and securely grounded to the vehicle chassis
using the correct wire sizes.

l

Install terminal covers and make sure there are no exposed conductors.

Содержание Freedom e-GEN

Страница 1: ...nt is well ventilated In case of fire use only a Class ABC type dry chemical fire extinguisher Water can be a dangerous extinguishing medium for energized equipment because of the risk of electrical shock Dispose of Xantrex Batteries through a local recycling center Do not mix batteries with other wastes Contact your local recycling center for proper disposal information Failure to follow these in...

Страница 2: ...zes 10 Make the system communication connections between all system devices using the provided system wiring harness 881 0042 12 Use the labels on the wiring harness as a guide and follow the System Diagram for Communication Connection Follow the vehicle manufacturer s instructions when wiring to the vehicle s ignition circuit 11 End devices in the CANbus network must both be terminated with a 120...

Страница 3: ... 4 0 Chassis battery 90 2 cable is from the Device to the DC busbar free air 30 C ambient Table 3 Minimum system DC cable size requirements l Use DC cables with a higher insulation temperature rating 105 C if possible However a higher insulation temperature rating does not mean the conductor size can be reduced due to the temperature ratings of the terminal connections Always use a qualified insta...

Страница 4: ...ion purposes only Always use a professional installer that satisfies the requirements for a qualified personnel Failure to follow these instructions can result in damage to equipment NOTE The diagram is for information and illustration purposes only Images are not to scale The system diagram is not intended to guide the actual placement of equipment Read and follow DC Cable and Fuse Requirements s...

Страница 5: ...C BLADE System Diagram for Communication Connection EQUIPMENT DAMAGE The system diagram is for information and illustration purposes only Always use a professional installer that satisfies the requirements for a qualified personnel Failure to follow these instructions can result in damage to equipment NOTE The diagram is for information and illustration purposes only Images are not to scale Route ...

Отзывы: