Installing the Auto Gen Start
975-0082-01-01
2–19
Type 10
Type 10 is a StartStop mode configuration with no preheat signal or
shutdown bypass functionality.
Figure 2-11
Type 10 connection diagram
Table 2-11
Type 10 relay and timing preset configurations
Relay 1 mode
StartStop
Relay 3 mode
No function
Gen Run signal hold time
0.5 s
Preheat time
0 s
Preheat to crank delay
0 s
Crank time
15 s
Crank retry time
30 s
Shutdown bypass time
0 s
Start tries
3
18
17
START
16
14
13
12
GEN RUN SIGNAL
GROUND
STOP
Relay 1
Relay 2
5A fuse
5A fuse
AGS wiring harness
Generator wires
Complete overcurrent protection
not shown. Refer to page 2–6.
Содержание Automatic Generator
Страница 1: ...Automatic Generator Start Owner s Guide...
Страница 2: ......
Страница 3: ...Automatic Generator Start Owner s Guide...
Страница 8: ...vi...
Страница 22: ...1 8...
Страница 54: ...Configuration 3 6 975 0082 01 01 Figure 3 5 Auto Gen Start menu contents...
Страница 102: ...A 4...
Страница 118: ...WA 6...
Страница 122: ...IX 4...
Страница 123: ......