MomentaryRun Mode
975-0082-01-01
C–3
MomentaryRun Mode
For generators with MomentaryRun mode starting types (Type 11):
•
Relay 1 (Run/Stop relay) can be used for two-wire configured
generators.
•
Relay 2 has no unique function in this configuration, but it is easiest
to leave it doing the cranking so that another configuration is not
required for it.
•
Preheat will generally not be used in this configuration.
•
The Preheat will never overlap the Crank Time.
•
The “Delay” refers to the “Preheat to Crank Delay” and may be zero.
•
Cranking will cease when the generator run signal goes high for the
specified hold time or when the crank time has elapsed.
Figure C-2
MomentaryRun mode timing diagram
Stop
Run
Time
Relay1: Momentary Run
Relay2: Start (Cranking)
Relay3: Preheat (Glow)
Crank
Start
Preheat
Содержание Automatic Generator
Страница 1: ...Automatic Generator Start Owner s Guide...
Страница 2: ......
Страница 3: ...Automatic Generator Start Owner s Guide...
Страница 8: ...vi...
Страница 22: ...1 8...
Страница 54: ...Configuration 3 6 975 0082 01 01 Figure 3 5 Auto Gen Start menu contents...
Страница 102: ...A 4...
Страница 118: ...WA 6...
Страница 122: ...IX 4...
Страница 123: ......