Cold location controller for top-hat rail installation with enhanced operating modes for 4 cold locations

4

CRC-BL_V2.4.0_PI_2021-02_DE

Subject to technical changes

CRC-BL

1.5 

Installing the device

This device is designed for top-hat rail installation. The housing has standard DIN 43880 dimensions

and is also suitable for operation in fuse boxes and distribution cabinets.
The device can be positioned immediately adjacent to another device without gaps.

WARNUNG

DANGER TO LIFE FROM ELECTRIC SHOCK AND/OR FIRE!

Switch off the power to the entire plant before installing. Otherwise, mains voltage and/or exter-
nal voltage may still be present, even if the control voltage is switched off. Always remove both
power plugs (L and N).

The entire plant must be free of voltage.

1.

(A) 

Place the device with the leading edge at an acute angle to the top-hat rail.

2.

(B)

 Push the device downwards onto the top-hat rail.

The device snaps into place with the fastening safety catch 

(a)

 on the top-hat rail.

You can now connect the device.

Fig. 3: Top-hat rail installation

1.6 

Technical data

Power supply

230V~, +10% / -15%, max. 8VA

Display

1 x display with plain text display

2 x green LED, C-BUS data traffic (CAN Tx, CAN Rx)

C-BUS communication

3-conductor CAN bus interface with integrated power supply, gal-

vanically isolated

Temperature sensor

4 x TRK277/7 PLUS, DGF

(T2015, T3000, TF201/TF231, K243)

Digital inputs

4 x floating

Output relay

4 x normally open contacts, 230V~, 4(2)A

Real-time clock

Battery-buffered

Monitoring system

Monitoring of data memory and connected sensors

Dimensions

(W x H x D) 106mm x 90mm x 58mm (DIN 43880)

Fastening

Top-hat rail TH 35-15 or TH 35-7.5 (DIN EN 60715)

Ambient temperature

Operation: 0...+55°C, storage: -25...+70°C

Weight

About 450g

CE conformity

-

2014/30/EU (EMC Directive)

-

2014/35/EU (Low Voltage Directive)

EAC conformity

-

 TR ZU 004/2011

-

 TR ZU 020/2011

RoHS II

Valid from

Version 2.4.0

A

B

Содержание CRC-BL

Страница 1: ...r defrost hot gas defrost and cool gas defrost Defrost control by real time clock with power reserve Simple defrost synchronisation of multiple controllers master slave 8 defrost times by integrated weekly timer Digital inputs for setpoint switchover manual defrost initiation and door contact Option to select 3 point control Control sensor weighting can be set separately for day operation and nigh...

Страница 2: ...or purposes other than the intended purpose WARNUNG DANGER TO LIFE FROM ELECTRIC SHOCK AND OR FIRE Switch off the power to the entire plant when carrying out installation wiring or removal work Otherwise a mains voltage and or external voltage may still be present even if the control voltage is switched off Always remove both power plugs L and N The wiring of the device must be carried out only by...

Страница 3: ... wurm de 1 4 Connection diagram Fig 2 Connection diagram Version Date V2 4 0 and higher 2021 02 Documentation status Pos Designation Function 1 C BUS interface Data communication H CAN high S shield L CAN low 2 Output relays K1 K4 Dependent on cold location type floating contact 230V 4 2 A 3 Power supply L 230V 50Hz 4 Power supply N Neutral conductor 5 Digital inputs Di1 Di4 Dependent on cold loca...

Страница 4: ...p hat rail 2 B Push the device downwards onto the top hat rail The device snaps into place with the fastening safety catch a on the top hat rail You can now connect the device Fig 3 Top hat rail installation 1 6 Technical data Power supply 230V 10 15 max 8VA Display 1 x display with plain text display 2 x green LED C BUS data traffic CAN Tx CAN Rx C BUS communication 3 conductor CAN bus interface ...

Отзывы: