DIQ/S 28X
Overview
11
ba77168d02
03/2017
Components to
extend the sys-
tem?
Branches
To be able to connect more sensors than there are SENSORNET connections
available at a Universal Transmitter DIQ/S 28X, use the branching module DIQ/
JB (accessory). The DIQ/JB branching module is a simple passive module for
the branching of IQ S
ENSOR
N
ET
lines.
Relay and current
outputs
The relay and current outputs can be linked with sensors. Linked outputs can be
used to monitor sensors and for the output of measured values.
A relay output can be programmed as:
Monitoring relay
Limit monitor
Proportional output of measured values (pulse width or frequency output)
Control unit of a sensor cleaning system driven by compressed air.
A current output (system variant or extra component -CR3 or -CR6)
is program-
mable as:
Analog output
PID controller
Function
Component
Passive
compo-
nents
Power supply module
MIQ/PS
Radio link (with power supply unit) MIQ/WL PS
Branching
(interfaces for sensors)
DIQ/JB, MIQ/JB
Active
compo-
nents
Relay
DIQ/CR3, MIQ/CR3,
MIQ/R6
Current outputs
DIQ/CR3, MIQ/CR3,
MIQ/C6
Current inputs
MIQ/IC2
More
compo-
nents
Valve output
DIQ/CHV, MIQ/CHV Plus
Maximum extensibility of the system:
Passive components: no limitation
Valve outputs: maximum 1 output per sensor
Active components: 2
Example:
The variant DIQ/S 284-CR6[-XX] already contains one active
component (DIQ/CR3). The system can still be extended by one
active component.
Содержание DIQ/S 282