Settings
MIQ/CR3; DIQ/CR3
4 - 34
ba64107e08
05/2006
Within the proportional band, a concentration increase by 1 mg/l
causes a decrease of the current output by 1 mA. If, for example, the
measured concentration is 5 mg/l, 11 mA are output:
The highest concentration with which the controller works within the
proportional band is 8 mg/l (corresponding to
Imin =
8 mA), the lowest
one is 2 mg/l (corresponding to
Imax =
14 mA).
Settings
(
)
µγ/λ
4
µγ/λ
5
µγ/λ
µΑ
1
µΑ
12
Ι
Χοντρολλερ
−
⋅
−
=
(
)
µΑ
11
µγ/λ
1
µγ/λ
µΑ
1
µΑ
12
Ι
Χοντρολλερ
=
⋅
−
=
Setting
Selection/Values
Explanation
Measured variable
Main variable
Adjoining variable
Main variable
designates the actual
measured parameter
of the sensor (e.g.
pH, oxygen, etc.).
Adjoining variable
designates an
additional measured
parameter (e.g.
temperature).
Nominal value
within the measuring
range (sensor-
dependent)
Nominal value the
measured value is
regulated to
Xp
5 ... 100 %
-5 ... -100 %
of the measuring
range
Proportional band of
the controller.
Negative values
result in a negative
characteristic curve.
Imin
0 ... 20 mA
Lower current
limitation *
Imax
0 ... 20 mA
Upper current
limitation *
* Note:
Spacing between
Imin
and
Imax
:
at least 5 mA