6-23
Configuration Options
•
Service Access:
Determines whether this account will be able to access command
mode via Serial Port, Telnet/SSH or Web and whether or not the account will be
allowed to initiate outbound connections. For example, if Telnet/SSH Access is
disabled for this account, then this account will not be able to access command
mode via Telnet or SSH. (Default = Serial Port = On, Telnet/SSH = On, Web = On,
Outbound Access = Off.)
Note:
The Service Access Parameter is only used to select permitted access
services for an individual user account. To separately enable/disable all SSH or
Telnet Access for the VMR/NPS unit, please refer to Section 6.8.
•
Current/Power Metering:
(VMR Only) Enables/Disables current and power
metering for this account. When disabled, this account will not be able to view
current or power readings or display current or power history. Note that in order
for accounts to be able to display these logs, Current and Power Metering must be
enabled via the Systems Parameters menu as described in Section 6.2.
(Default = On.)
Note:
Current and Power Metering functions are not available on NPS units.
•
Callback Phone Number:
Assigns a number that will be called when this account
attempts to access command mode via modem, and the Callback Security
Function has been enabled as described in Section 6.2.4. (Default = undefined.)
Notes:
• If the Callback Number is not defined, then Callbacks will not be performed
for this user.
• If the Callback Number is not defined for a given user, and the Callback
Security feature is configured to use either of the "On - Callback" options,
then this user will be granted immediate access to command mode via
modem.
• If the Callback Number is not defined for a given user, and the Callback
Security feature is configured to use the "On - Callback ONLY" option, then
this user will not be able to access command mode via Modem.
• When using the "On - Callback (With Password Prompt)" option, it is
important to remember that accounts that do not include a callback number
will be allowed to access command mode without callback verification.