Original Operating Instructions
BATx0100-ES-1-400-1
Installation
O_BATx0100-ES-1-400-1_V3.1_GB
Page
39
of
73
3.5.1.7 Option Interface for SBB16-10
With the option interface for SBB16-10, a connected SBB16-10 can be switched on
and off remotely. The connection is done at the screw-type terminals in the lower left
area of the cabinet. The screw-type terminals are designed for conductor cross-
sections of
16 mm²
to
70 mm²
.
Required material:
•
Programmable logic controller (PLC) (not included in scope of delivery)
•
Voltage supply source (not included in scope of delivery)
The supply voltage must be able to permanently supply 24 V
DC
/5 A and a maximum
current of 8 A for 0.1 ms
Figure 17: Connection option
interface
for SBB16-10
Pos. Description
1
Supply voltage connection (-X10)
2
Screw-type terminal (-X13.1) DC (+)
3
Screw-type terminal (-X13.2) DC (-)
4
PLC connection (-X11)
Procedure:
1.
Connect
the DC cables as follows:
o
DC (+)
to the grey screw-type terminal (-X13.1),
tighten
the screw with
6-8 Nm
.
o
DC (-)
to the blue screw-type terminal (-X13.2),
tighten
the screw with
6-8 Nm
.
2.
Connect
supply voltage and PLC as shown in Figure 18.