Original Operating Instructions
BATx0100-ES-1-400-1
Installation
O_BATx0100-ES-1-400-1_V3.1_GB
Page
40
of
73
Figure 18: Connection supply voltage and PLC
Output
signal
Connections Description
Values
Feedback On (-X11.1)
DC links are connected
24 V
DC
, max. 10 mA
Feedback Off (-X11.2)
DC links are disconnected
24 V
DC
, max. 10 mA
Feedback
Trip
(-X11.3)
Circuit breaker tripped
24 V
DC
, max. 10 mA
Feedback EN (-X11.6)
Enable signal
24 V
DC
, max. 5 mA
Input
signal
Connections
Description
Set values:
Control On
(-X11.4)
Connect DC links
24 V
DC
, min. 20 ms,
input resistance: 93 k
Ω
Control Off
(-X11.5)
Disconnect DC links
24 V
DC
, min. 20 ms,
input resistance: 93 k
Ω
Programming PLC:
The positive edge of the “Control On” input signal on the terminal (-X11.4) connects the
DC links between the BAT and SBB16-
10. The positive edge of the “Control Off” input
signal on the terminal (-X11.5) disconnects the DC links between them.
“Control On” and “Control Off” signals must be inverted to each other.
NOTICE: DC links may only be connected if the signal “Feedback EN” is present.
Содержание BAT 0100-ES-1-400-1 Series
Страница 73: ......