3
Installation
IMPORTANT:
Consult local and general regulations before performing dryer installation. Make certain the electrical network is not
overloaded. Do not connect to a branch circuit with a circuit breaker or fuse rated over 20 Amps. This is a UL recommendation and
complies with NEC.
1. Disconnect the power source.
2. Use the security hex key supplied to remove the three cover-mounting screws. Remove the cover from the dryer.
3. Place the template against the wall at the desired location, use information in Table 1 to determine the recom mended mounting
height. When two or more dryers are installed, they should be placed no closer than 24” (60 cm) from center to center. Mark the
location of the four mounting bolt holes and the wire entry hole.
4. For recessed wiring, carry the supply wire to the dryer baseplate knockout and attach with an acceptable cable clamp. The dryer
requires two con ductors for power plus a separate ground wire.
5. For surface wiring, remove one of the two knockouts located at the bottom corners of the air intake. Pass the supply wire according
to local code, through the knockout and attach it securely to the bracket. The bracket may be relocated to the opposite side of the
dryer if desired. The dryer requires two conductors for power plus a separate ground wire.
6. Attach the mechanism firmly to the wall. For wood walls or wood studs, use No. 16 screws of proper length to ensure 1” (25 mm)
minimum stud penetration. For masonry walls use expansion bolts or anchors for 1/4” (6 mm) screws of proper length to ensure
penetration 1/4” (6 mm) deeper than anchor. Shim if necessary to ensure that the baseplate is level and flat against the wall.
7. Connect the supply wires to the terminal block where indicated. Connect the ground wire to the baseplate with the ground screw.
8. Replace the cover.
Do not overtighten the screws.
NOTE:
The security hex key should be retained by the service engineer and not the user to prevent unqualified servicing.
INSTALLATION MUST BE PERFORMED BY QUALIFIED ELECTRICAL PERSONNEL.
Recommended Mounting Heights
from Bottom Edge of Dryer
in. (cm.)
Men’s washrooms
49 (126)
Women’s washrooms
47 (119)
Children’s washrooms, ages 4-7
35 (88)
Children’s washrooms, ages 8-10
39 (99)
Children’s washrooms, ages 11-13
43 (109)
Children’s washrooms, ages 14-16
47 (119)
Handicap Mounting Height
37 (94)
Table 1 - Recommended Mounting Heights
Maintenance
Proper maintenance should be pre formed on the units at least every 6 months under normal use.
CLEANING
Cleaning and maintenance must be performed by qualified electrical personnel.
1. Disconnect the electrical supply.
2. Use the security hex key to remove the three cover-mounting screws.
3. Remove the cover.
4. Clean all dust and lint from the interior of the dryer.
5. Replace the cover. Do not over-tighten the screws.
6. Wipe the cover with a damp cloth. Never use abrasives to clean the cover.
Figure 1 – Wiring Diagram
Control Circuit
PCB & Sensor
Heating
Element
Heating
Element
This appliance must be grounded