3600W Digital Inverter with Pure Sine Wave
AFTER SALES SUPPORT
e-mail: [email protected]
1800 909 909
MODEL: №. INF3800A-1 • 03/2018 • 59905
(toll free)
AFTER SALES SUPPORT
(toll free)
3600W Digital Inverter with Pure Sine Wave
e-mail: [email protected]
1800 909 909
MODEL: №. INF3800A-1 • 03/2018 • 59905
38
39
AC output:
240Vac ~ 50Hz
Rated power:
3400W +/- 5%
Peak power:
3600W +/- 5%
Phase:
Single
Power factor:
cos
φ
=1
Displacement:
182cc
Motor:
4 stroke
No load speed:
3000 RPM
Approximate Generator
Run time:
(Hours per full tank)
Full Load:
3 hours 20 mins
50% Load:
7 hours 10 mins
25% Load:
11 hours 50 mins
Fuel tank capacity:
10.5L
Fuel type:
Unleaded
Oil tank capacity:
600ml
Oil type:
4 Stroke (SAE 10W-30)
Net weight:
31kg
(with wheels and handle)
Spark plug:
NGK BPR6ES
Product Dimensions:
(without wheels or carry handle) 52cm x 41cm x 46cm (L x W x H) +/- 10%
Noise rating:
72 dB (A) (taken at 7 metres)
You must wear ear protection at all times.
This product complies with:
Safety – AS 3010
For other issues not covered in this chart, please call Customer Service on 1800 909 909.
Troubleshooting
Specifications
Trouble
Possible cause
Suggested remedy
No electrical output
1. Faulty receptacle
1. Have service centre replace receptacle
2. Overload has been triggered
(red Overload light on).
2. Remove all appliances. Stop the
generator, and restart. Reconnect
appliances but with reduced load.
3. Faulty power cord
3. Have an electrician replace cord.
4. 240Va.c Outlet Power On/Off switches
(1/2) turned off.
4. Check the 240Va.c Outlet Power On/
Off switches (1/2) are “ON”.
Repeated overload
1. Overload
1. Reduce load
2. Faulty cords or equipment
2. Check for damaged, bare, or frayed
wires on equipment. Replace.
Generator overheating
1. Generator overloaded
1. Reduce load
2. Insufficient ventilation
2. Move to adequate supply of fresh air
Generator keeps stopping,
or is operating rough
1. Check oil level
1. Add oil so oil is at the correct level.
Refer page 21-22 of this manual.
2. Generator not sitting on flat
and level surface
2. Move generator to a level and
flat surface
3. Motor needs to be cleaned of carbon
3. Remove, check and clean spark
arrestor (11) if needed.
Remove, clean or replace spark plug (23)
Specifications
Troubleshooting Cont: