Worcester GREENSTAR II HE OIL 12/22 Скачать руководство пользователя страница 18

18

11.1 

After unpacking the appliance it is recommended that the

top and front cabinet panels are removed, as described in Section
5, and stored in a safe place to avoid damage during installation
and allow easy inspection for any leaks after the system has
been filled.

11.2 

Remove the burner as described below and store in a safe

place until the appliance is ready for commissioning.

1. 

Remove the air tube from the burner by loosening the jubilee

clip and pulling the tube up and away.

2.

Remove the 13mm nut at the top of the burner and pull the

burner out, taking care not to put any tension on the electrical
cable.

11.3 Flue system installation.

Install the appliance flue system as described in Section 7.

11.4 Heating system installation.

Before the appliance is fitted to the heating system

flush the system and mains water supply.
1. 

Plumb the boiler into the central heating system. 

2. 

Check that all unused sockets have been plugged.

3.

Fit the auto air vent to the boiler.

4. 

Fill the system and vent all radiators and high points to

remove air from the system.

5. 

Check the boiler and all pipework connections for leaks.

11.5 Oil supply installation.

(See Fig. 16).

NOTE: 

Never route the oil supply pipe/hose directly below the

combustion chamber base.

NOTE: 

Connection of rigid copper pipe to the oil pump is not rec-

ommended. Connection to the oil pump should be made with
flexible oil hoses.

(a) Single pipe suction lift with de-aerator.

For connection of single pipe suction lift with de-aerator follow
the procedure as for a double pipe system as described below.

(b) Double pipe system oil return pipe.
1. 

fit the oil return pipe, from the tank, down the left hand side

of the boiler along the base. Terminate the end approximately
200mm from the front of the base.

2. 

Connect a flexible hose, of the same type as the one supplied, to

the pipe using a suitable adaptor.
Ensure that the connections are properly sealed.

3. 

Fit the oil supply pipe as described in the following section.

(c) Single pipe system oil supply pipe.
1. 

Bend a piece of 10mm or 12mm copper tube (as selected) to

the correct profile to allow the pipe to be fed down the side of
the appliance. The pipe may be routed along either the right or
left hand side of the boiler as required. When using 12mm pipe
fit a 12mm to 10mm compression coupling and connect to the
valve with a short piece of 10 mm pipe, otherwise connect direct
to the valve. 

Note: 

never use soldered joints on oil supply pipes as this could

cause a hazard in the case of a fire.

2. 

Route the pipe back to the oil supply tank ensuring that it is

hard against the boiler, to allow installation of the side panel.

3. 

With the isolating valve in the correct orientation tighten the

back-nut.

4. 

Turn the isolating cock fully clockwise to close the valve.

5. 

Open the main oil supply valve at the tank and check for any

leaks.

6. 

Place a suitable container below the bulkhead fitting and

open the valve.

7. 

Draw off at least 2.5 litres of oil until a steady flow of clear

uncontaminated oil can be seen and turn off the isolating valve.

Note: 

This method may not be possible on some installations

where a sub-gravity system is used. Where this problem arises
bleed the system using the oil pump as described in Section 12
and remove and clean the oil pump filter to remove any debris
collected as a result of installation.

11.6 

Replace the electrical control panel and side panels in

reverse order to the removal procedure of Section 5 and connect
the electrical supply as described in Section 10.

11.7 Condense drain connection

When connecting the condensate drain to the waste water
drain, it is essential to maintain a downwards slope towards the
waste drain.

Note: 

The maximum production of condensate is 1.5 L/h. This

flow rate does not require any specific treatment.

11. Installation

Fig. 25. Frost Protection.

Содержание GREENSTAR II HE OIL 12/22

Страница 1: ...CE INSTALLATION AND SERVICING INSTRUCTIONS BOILER OUTPUT Hot Water and Central Heating 12 22 MINIMUM 12 kW 41 000 Btu h MAXIMUM 22 kW 75 000 Btu h THESE INSTRUCTIONS APPLY TO UK MODELS ONLY THESE INST...

Страница 2: ...mentioned in the instructions 2 1 These instructions cover room sealed balanced flue RS appli ances only 2 2 The Worcester Greenstar HE Oil appliance covered in these instructions has been designed to...

Страница 3: ...22 Table 2 Electro Oil Bentone Sterling 40 Burner See Fig 27 RS Balanced Flue Appliance Fuel Nozzle Pump Pressure p s i Fuel Flow Rate Flue Gas Temp C CO2 Approx Air Setting Appliance Input kW Btu hr...

Страница 4: ...e rear of the connector protecter plate and hinge up and away 5 4 The control box can be removed by undoing the two screws in the top access cover two screws in the front two ball studs in the top and...

Страница 5: ...rt 6 Condensate drain 7 Heat exchanger drain point 8 Burner air inlet pipe 9 Oil Burner 10 Lock out reset button 11 Sight glass 12 Boiler shell 13 Auto air vent connection 14 Heating flow 15 Heating r...

Страница 6: ...condensation boiler Air is drawn in by the burner s fan from outside the appliance through the hose connected to the air inlet and combustion product evacuation concentric tube The boiler shell equipp...

Страница 7: ...ccess a suitable terminal guard must be fitted A suitable guard is available from Worcester Heat Systems Part Number 7 716 190 009 or alternatively a proprietary terminal guard may be used provided it...

Страница 8: ...nd two 45 Bends Fig 9 Flue with two 90 Bends Fig 10 Flue with one 90 and two 45 Bends Fig 11 Vertical Flue Fig 12 Vertical Flue with two extra 90 Bends Fig 13 Vertical Flue with two extra 45 Bends 125...

Страница 9: ...minal Not allowed 1200 K Vertically from a terminal on the same wall Not allowed 1500 L Horizontally from a terminal on the same wall Not allowed 750 M Above an intersection with the roof 600 Not appl...

Страница 10: ...double pipe system or single pipe system with de aerator is being installed Selection of the correct pipe diameter will depend on the position of the oil stor age tank relative to the burner and the l...

Страница 11: ...l H 4 m 13 ft maximum Fire valve to BS 5410 Fire valve to BS 5410 Isolating valve Isolating valve Fire detection element Filter Burner Burner Wall Wall b Double pipe system Isolating valve Non return...

Страница 12: ...plan Expansion Vessel Diverting valve Pump Radiator N B A drain cock should be installed at the lowest point of the heating circuit Domestic hot water cylinder Pressure gauge Safety valve To system f...

Страница 13: ...er or plastic pipe can be used The plastic pipe must be manufactured to BS 7291 and installed to BS 5955 part 8 It is important to protect the system components the plastic pipe specified must be resi...

Страница 14: ...5 Safety Check In the event of an electrical fault after the installation of the appliance the electrical system shall be checked for short circuits fuse failure or incorrect polarity of connections 1...

Страница 15: ...3 4 5 6 7 8 9 Brown Blue Blue Brown Black Plug in connector Brown Brown Orange 1 C Blue Green Yellow Blue White Grey L N E E N 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 Mains supply 230V 50Hz Brown Fig 21 Pro...

Страница 16: ...to P Remove link 1 to 3 Optional Worcester Programmer HEAT SYSTEMS HEATING ADVANCE OFF TWICE ONCE ON OFF TWICE ONCE ON SELECT LOCK SET YES SELECT PM TUE HOT WATER ADVANCE 10 WAY JUNCTION BOX NOTE If...

Страница 17: ...ue Brown Brown Orange Grey Blue Green Yellow Green Yellow Brown Green Yellow 7 8 910 Fig 24 Honeywell Y Plan NOTE When using a WHS programmer remove the orange wire from terminal 9 and connect to term...

Страница 18: ...one supplied to the pipe using a suitable adaptor Ensure that the connections are properly sealed 3 Fit the oil supply pipe as described in the following section c Single pipe system oil supply pipe 1...

Страница 19: ...s and reset the burner control box Repeat the procedure at least three times or until a steady stream of oil without air is exhausted from the bleed port Re lock the bleed port Two Pipe System A two p...

Страница 20: ...ce has been installed in a compartment check that the ventilation areas are clear 11 Clean all oil filters Some of the servicing points are covered more fully in the following instructions 14 2 Pre Se...

Страница 21: ...any debris Discard the check valve if the holes cannot be cleared or if the unit is defective and replace with a new one e Replace in the reverse order 5 It is strongly recommended that the oil atomi...

Страница 22: ...within the appliance case Test the operation of the fire valve to ensure that the mechanism operates and that the oil supply is completely isolated 14 9 Recommission the Burner 1 Connect the flexible...

Страница 23: ...R Boiler Shell Cover Equipped FCX Greenstar HE Oil 12 22 V 72 28389 8 716 103 289 0 31 BOILER Sealing AMF34D 30 x 21x 3 E 20 03889 8 716 103 290 0 32 BOILER Pipe Return FCX Greenstar HE Oil 12 22 U 72...

Страница 24: ...24...

Страница 25: ...ing out high limit control and exhaust thermostats Programmer open circuit Check by linking 1 and 2 on the connector Faulty control box Replace if necessary Flue draught incorrect Check flue draught C...

Страница 26: ...26...

Страница 27: ...27...

Страница 28: ...changed in the interests of continued improvement All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application PUBLICATION TTGB 8 716 114 728a 11 07 Wo...

Отзывы: