CON
VE
R
S
ION
K
ITS
INSTALLATION & SERVICING INSTRUCTIONS
44
L.P.G. CONVERSION
6-720-611-730b (12.05)
Change code plug:
1 Unclip cover panel (A) from base as shown
2 Unscrew and remove panel (B).
3 Remove and dispose of old code plug.
4 Replace with new conversion code plug (C).
N.G. code plug number 421
L.P.G. code plug number 422
Reposition panel (B) and secure with screw.
Clip cover panel (A) back into place.
Change gas pipe:
5 Rotate gas pipe (D) anti-clockwise, pull
upwards and remove gas pipe.
6 Replace with new conversion gas pipe (E),
push downwards and rotate clockwise to lock
into position.
Conversion label:
Replace existing label with new conversion
label.
Adjust the CO² level:
See 'Setting the gas/air ratio' under
Servicing &
Spares
section.
L.P.G. CONVERSION
A
B
D
3
4
5
6
a
C
E
b
c
a
b
c
2
1