INSTALLATION & SERVICING INSTRUCTIONS
21
FLUE INSTALLATION
FLUE INSTALLATION
6-720-611-730b (12.05)
1 Remove retaining screw (B) to swing control
panel assembly (A) outwards to its full extent.
2 Remove screws (C) from inside of casing.
Lift front of panel (D) to release.
Pull forwards to disengage rear retainer (E),
then lift panel (D) away from boiler.
3 Pull clip (F) outwards to release expansion
vessel (G).
4 Swing expansion vessel (G) outwards.
Note: for easier access to the inner case, the
expansion vessel can be unhooked (by removing
the retaining screw on the hinge) lowered and
moved to the side. Take care not to overstretch
the flexible pipe connections.
5 Release four screws (H) to remove the inner
case cover (J).
CONVERT FROM REAR FLUE OUTLET:
The boiler is supplied ready to fit a rear flue outlet.
To flue vertically or from the side of the boiler,
follow the procedure below:
Remove one of the outer casing 'knock-out'
panels (K) for left, right or vertical flue fitting.
Loosen blanking plate screws (L) from inside
the inner boiler case (P).
Rotate blanking plate (M), complete with
gasket, to disengage and remove from the
outside.
Refit blanking plate (M) over rear flue outlet
and tighten screws (L).
2
5
4
3
F
G
D
P
M
L
K
B
1
E
A
H
J
C
G
C