![Woodward SPM-D2-10 Скачать руководство пользователя страница 61](http://html1.mh-extra.com/html/woodward/spm-d2-10/spm-d2-10_manual_995878061.webp)
Manual 37615C
SPM-D2-10 - Synchronizing Unit
© Woodward
Page 61/68
Appendix C.
List of Parameters
Product number
P/N _____________________________ Rev _______________________________
Version
SPM-D2-10 ____________________________________________________________
Project
_____________________________________________________________________
Serial number
S/N _______________
Date
______________________________
Option
Parameter
100/400V; 1/5 A
Adjustment range
Default
setting
Customer settings
CONFIGURE GENERAL PARAMETERS
SPRACHE/LANGUAGE
German/Englisch
English
G
E
G
E
Software version
7.10-0
Enter code
0000 to 9.999
XXXX
Enter code
Protection
ON/OFF
OFF
on
off
on
off
Reset on Factory Defautls
YES/NO
NO
Y
N
Y
N
Allow Factory Defaults
YES/NO
NO
Y
N
Y
N
CONFIGURE BASIC SETTINGS
Rated Frequency
fn
48.0 to 62.0 Hz
50.0 Hz
Generator freq.
Setpoint
48.0 to 62.0 Hz
50.0 Hz
Gen. voltage
secondary
[1]50 to 125V/
[4]50 to 440V
100/400V
Mains voltage
secondary
[1]50 to 125V/
[4]50 to 440V
100/400V
Gen. voltage
primary
[1,4] 0.1 to 65.0 kV
0.1/0.4 kV
Mains voltage
primary
[1,4] 0.1 to 65.0 kV
0.1/0.4 kV
Rated voltage
Vn
[1] 50 to 125 V/
[4] 70 to 440 V
100/400 V
Gen. voltage
Setpoint
[1] 50 to 125 V/
[4] 70 to 440 V
100/400 V
CONFIGURE CONTROLLER
Automatic idle
Running
ON/OFF
OFF
on
off
on
off
Terminal 6
Release control/OFF
Release con.
f control type
THREEP/ANA./PWM
ANALOG
Freq. controller
ON/OFF
ON
on
off
on
off
Freq. controller Isol. oper
ON/OFF
OFF
on
off
on
off
Freq. Controller
Ramp
0.1 to 99.9 Hz/s
5.0 Hz/s
Freq. controller Dead band
0.02 to 1.00 Hz
0.10 Hz
Freq. controllerTime pulse>
10 to 250 ms
80 ms
Freq. controller
Gain Kp
0.1 to 99.9
15.0
f control output
refer to table under
+/-20 mA
(+/-10 V)
f control output Level PWM
3.0 to 10.0 V
10.0 V
PWM-signal Logic positive
positive/negative
positive
f control output Init.state
0 to 100 %
50 %
f control output
(max.)
0 to 100 %
100 %
f control output
(min.)
0 to 100 %
0 %
Freq. controller
Gain Kp
1 to 240
15
Freq. controller Reset Tn
0.0 to 60.0 s
2.5 s
Freq. controller Derivat.Tv
0.00 to 6.00 s
0.00 s
V contr. type
THREESTEP/ANALOG
ANALOG
Volt. controller
ON/OFF
ON
on
off
on
off
Volt. controllerIsol. oper.
ON/OFF
OFF
on
off
on
off
Volt. controller
Ramp
1 to 99 V/s
25 V/s
Volt. controller Dead band
[1] 0.1 to 15 / [4] 0.5 to 60
V
[1] 1 / [4] 2
V
Volt. controllerTime pulse>
20 to 250 ms
80 ms