Manual 37615C
SPM-D2-10 - Synchronizing Unit
Page 22/68
© Woodward
Table for Terminal 6 if Configured "OFF"
The SPM-D2-10 and 10/X may be used as an ASG 410+ by de-energizing terminal 6.
The status of the discrete inputs "Reply: CB open" (terminal 4) and "Enable CB" (terminal 3) is displayed on the
face of the controller via the LEDs "GCB closed" and "Enable GCB" respectively. In addition to the state of the
discrete input signals, the conditions in Table 5-3: Operating conditions - terms will affect the controller as fol-
lows:
Input signal
Operating condition
Cond.
Relay "Command: close CB"
(terminals 14/15)
LED
"Ge
n
-CB
ON"
LED
"Ge
n
CB f
re
e"
Disc
r.
in
p
.
te
rm
.
5
:
"En
ab
le
iso
late
d
o
p
.
/
d
ea
d
b
u
s sta
rt"
Re
fe
r
to
0
0
x
OFF or
automatic no-load control
-
C1
OFF
OFF
0
1
0
No-load operation or
synchronization
C
A
OFF
Slip or phase match
0
1
1
No-load operation or
synchronization or
dead bus start
C
A
B
OFF
Slip or phase match
dead bus start
1
x
0
OFF
-
OFF
1
x
1
Isolated operation
D
OFF
0: "OFF" / 1: "ON" / x: Signal of no significance (0 or 1)
Table 5-2: Operating conditions - terminal 6 = "OFF"