Manual 37351A
MFR 11 Packages - Protection Relay
© Woodward
Page 51/59
Appendix D.
List of Parameters
Product number
P/N _____________________________ Rev _______________________________
Version MFR
11_______________________________________________________________
Project _____________________________________________________________________
Serial number
S/N _______________
Date
______________________________
Pkg.
Parameter
Setting range
100/400/690 V
Default setting
Customer setting
BASIC DATA
Software version
- -
SPRACHE/LANGUAGE
German/English English
G
E
G
E
Enter code
number
0000 to 9999
-
Password Protection
ON/OFF ON
1
0
1
0
Define level 1
code
0000 to 9999
0001
Define level 2
code
0000 to 9999
0002
Direct parametr.
YES/NO NO
Y
N
Y
N
MEASUREMENT
Volt.-Measuring
Phase to phase / Phase-neutral
Phase-neutral
pp
pn
pp
pn
Volt.transformer secondary
50 to 125/50 to 480 V
100/400 V
Volt.transformer primary
00.100 to 65.000 kV
00.400 kV
SC
SC+N
Volt.transformer sec.(GN)
50 to 125/50 to 480 V
100/400 V
..
Volt.transformer prim(GN)
00.100 to 65.000 kV
00.400 kV
..
Volt.transformer sec.(MN)
50 to 125/50 to 480 V
100/400 V
..
Volt.transformer prim(MN)
00.100 to 65.000 kV
00.400 kV
..
Rated voltage
5 to 125/10 to 480 V
100/400 V
SC
SC+N
Rated frequency
40.0 to 70.0 Hz
50.0 Hz
CONTROL FUNCTIONS
SC
SC+N
Synchronizing functions
ON/OFF ON
1
0
1
0
..
Synchronization df
max
0.02 to 0.49 Hz
0.18 Hz
..
Synchronization df
min
0.00 to -0.49 Hz
-0.10 Hz
..
Synchronization dV
max
0.1 to 15.0 %
6.0 %
..
Synchronization
Max phase <
1 to 60°
2°
..
Synchronization Time
pulse
50 to 250 ms
200 ms
SC
SC+N
Circuit breaker
Pick-up t.
40 to 300 ms
80 ms