Manual 37442B
LSG - Load Share Gateway
Page 30/32
© Woodward
Chapter 7.
Technical Data
Nameplate
1
P/N
Item number
2
REV
Item revision number
3
S/N
Serial number (numerical)
4
S/N
Serial number (barcode)
5
S/N
Date of production (year-month)
6
Type
Description (short)
7
Type
Description (long)
8
Details
Technical data
9
Approval Approvals
Ambient variables ---------------------------------------------------------------------------------------------
-
Power supply (SELV) ................................................................. 12/24 Vdc (8 to 40.0 Vdc)
Intrinsic consumption
......................................................................... max. 3 W
-
Degree of pollution ............................................................................................................. 2
-
Maximum Altitude ..................................................................................................... 3000m
-
Grounding ........................... Earth Ground Terminal # 3 galvanically connected to housing
Interface --------------------------------------------------------------------------------------------------------
RS-485 interface
.....................................................................................................
isolated
-
Isolation voltage ....................................................................................................... 500 Vac
-
Type ........................................................................................ Half duplex, max 38.4kBaud
-
Shield Termination ...........................................internal R||C against Ground (Terminal # 3)
CAN bus interface
..................................................................................................
isolated
-
Isolation voltage ....................................................................................................... 500 Vac
-
Version ................................................................................................................... CAN bus
-
Internal line termination ................................................................................... Not available
-
Shield Termination ...........................................internal R||C against Ground (Terminal # 3)
Analog Load Share Line --------------------------------------------------------------------------------------
.................................................................................................................................
isolated
-
Isolation voltage ....................................................................................................... 500 Vac
-
Input / Output type ............................................... Analog voltage in- / output, configurable
-
Internal Resistance ............................................................................................ configurable
-
Shield Termination ...........................................internal R||C against Ground (Terminal # 3)
Housing ---------------------------------------------------------------------------------------------------------
-
Type
aluminum .........................................................................
-
Dimensions (W × H × D)
.............................. approx. 141mm × 98.5mm × 21 mm
-
Wiring ................................................................................... screw-plug-terminals 2.5 mm²
-
Recommended locked torque ........................................................... 4 inch pounds / 0.5 Nm
use 60/75 °C copper wire only
use class 1 wire only or equivalent
-
Weight
................................................................... approx. 280 g
Protection -------------------------------------------------------------------------------------------------------
-
Protection system
..................................................................................IP20
-
EMC test (CE) ................................................ tested according to applicable EN guidelines