Manual 37442B
LSG - Load Share Gateway
© Woodward
Page 29/32
Functional Test
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Testing the CAN Bus Communication
If the connection between the easYgen and the LSG is working properly, the LSG is recognized as a further “ea-
sYgen” by the easYgen devices. The LSG appears with the address 16. If a second LSG is used for analog reac-
tive Load Share this will appear with address 15.
Testing the EGCP-2 Network Communication
If the connection between the EGCP-2 and the LSG is working properly
and
the easYgen is detected by the LSG,
the LSG is indicated on the EGCP-2 sequence display screen as an
EGCP-2 Slave
with device number 8.
Testing the CAN Bus Communication (GCP/MFR)
If the connection between the GCP/MFR and the LSG is working properly, the LSG is recognized as a further
“GCP/MFR” by the GCP/MFR devices. The LSG appears with the address 8.